Wire the terminal block as shown in Fig. 5:
1. For single wires, strip 3/16 in. (5 mm); for multiple
wires going into one terminal, strip 1/2 in. (13 mm)
insulation from the conductor.
2. Insert the wire in the required terminal location and
tighten the screw to complete the termination.
3. Review and verify the terminal connection wiring
illustrated in Fig. 5.
Fig. 5. Connecting wires to the terminal block.
4. See Fig. 6 for wiring multiple Sylk devices.
TWO WIRES INTO ONE TERMINAL
1.
STRIP 1/2 IN.
1/2
(13MM) FROM
(13)
WIRES TO BE
ATTACHED AT
ONE TERMINAL.
2.
TWIST WIRES
TOGETHER
WITH PLIERS
(A MINIMUM OF
THREE TURNS).
DAISY-CHAINING MULTIPLE
SYLK DEVICES
TO CONTROLLER
TO SYLK DEVICE
Fig. 6. Options for wiring multiple Sylk devices.
M36289
WALL MODULE
TERMINALS
3.
CUT TWISTED END OF WIRES TO
3/16 IN. (5 MM) BEFORE INSERTING
INTO TERMINAL AND TIGHTENING
SCREW. THEN PULL ON EACH WIRE
IN ALL TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.
HOME RUNNING MULTIPLE
SYLK DEVICES
TO CONTROLLER
M36315
5. When wiring is complete, align the pins from the
front cover to the terminal block on the subbase.
6. Firmly push the front cover onto the subbase. If the
wall module is powered, a loading screen will be dis-
played.
Sylk Bus
The wall module communicates with the LCBS Connect
controller via Sylk, which is a two-wire, polarity-insensitive
bus that provides both 18 Vdc power and
communications. This enables a faster and cheaper
installation all while minimizing errors. The recommended
wire for Sylk is 18-24 AWG (0.82 to 0.20 sq mm) single
twisted pair, solid or stranded wire, unshielded for a
maximum distance from the controller of 200ft (60m).
Standard thermostat wire (non-twisted pair) can be used
for runs up to 100ft (30m). See Table 1.
Table 1. Maximun Distance.
Recommended maximum distance from
controller to any Sylk device
Single twisted pair, non-
shielded, stranded or solid
18-22 AWG
500 ft (150 m) 400 ft (120 m)
The wall module is intended to always communicate using
Sylk address 1 and is shipped from the factory with this
address configured. Other Sylk sensors are compatible
with the LCBS Connect controller and wall module but
limitations must be observed. Up to FOUR additional Sylk
sensors can be used unless a TR40-H, TR40-CO2 or TR40-
H-CO2 is used. Then the allowed additional sensors drops
to THREE. See Table 2 for a listing of the compatible Sylk
sensors.
Compatibility
The LCBS wall module has been designed specifically for
the LCBS controller. They are a one-to-one pair and
adding an additional LCBS wall module will result in a loss
of operation. Connecting an LCBS wall module to another
Honeywell controller will also result in the loss of
operation for the wall module.
3
LCBS CONNECT WALL MODULE
Standard thermostat wire,
(non-twisted), shielded or
non-shielded, stranded or
solid
24 AWG
18-24 AWG
100 ft (30 m)
31-00084EFS—01