Temperature limitation
The safety stop limits the temperature range to 38 °C.
The 38 °C limit can be overridden by pressing the button, see
fold-out page II.
Temperature limit stop
max.43°
If the temperature limit stop should be 43 °C, use
handel ref. No. 47 811, see fold-out page IV
Operation and settings,
see technical product information, 99.0409.xxx /
99.0438.xxx.
Activating setting mode
Disconnect the power supply to the electronics and reconnect
after 10 s.
The indicator lamp in the sensor system illuminates in setting
mode when the detection zone of the fitting is reached by an
approaching user.
Setting mode is automatically terminated after 3 minutes.
Fault / Cause / Remedy
Fault
Cause
Water not flowing
• Filter upstream of solenoid valve blocked
• Solenoid valve defective
• Plug-in connector without contact
• No voltage
- Battery discharged
(indicator lamp lights up continuously)
- Power supply unit defective
Undesired water
• Sensor system detection zone set too high
flow
for local conditions
• Automatic flushing activated
• Solenoid valve defective
Flow rate too low
• Mousseur dirty
• Filter upstream of solenoid valve dirty
• Filters in connection hose dirty
Water temperature
• Thermostat not adjusted to local pressure
too high or too
• Non-return valve defective
low
®
Bluetooth
Connection not
• No reception/connection interrupted
possible
• Interferences in the reception area
• Obstacle in transmission path
• Water is flowing / Object detection
Interrupted while
• Interferences in the reception area
operating
• Obstacle in transmission path
Maintenance
, see fold-out page III.
• Shut off hot and cold water supply.
• Disconnect voltage supply.
• Inspect and clean all parts, replace if necessary and
lubricate with special grease.
• Readjustment is necessary after each maintenance
operation on the thermostatic cartridge (see
"Adjusting").
Batteries which are almost discharged are displayed
by a flashing indicator lamp in the sensor system.
Replacement parts,
see fold-out page IV (* = special accessories)
,
Care
For directions on the care of this fitting, please refer to the
accompanying Care Instructions.
Remedy
- Clean filter
- Replace solenoid valve
- Check plug-in connector
- Replace battery
- Replace power supply unit
- Reduce range using remote control (special
accessory, prod. no.: 36 407) / app
- Wait 1 - 10 minutes
- Replace solenoid valve
- Clean or replace mousseur
- Clean filter
- Clean or replace filters
- Adjust thermostatic cartridge
- Replace the non-return valve
- Turn back the device to receiving range
- Turn off the source of interference
(observe manufacturer´s documentation)
- Remove from radio path
- The detection zone must kept clear
- Turn off the source of interference
(observe manufacturer´s documentation)
- Remove from radio path