Location and Clearances

All criteria given in the following sections reflect minimum
clearances. However, each installation must also be
evaluated, taking into account the prevailing local
conditions such as proximity and height of walls, and
proximity to public access areas.
The UltraTemp
®
Heat Pump must be placed to provide
clearances on all sides for maintenance and inspection.
1. At least 24 in. [610 mm] access must be available in
the front and 12 in. [305 mm] on all the other sides
of the heat pump for service and proper air flow.
(Manufacturer's recommendation).
NO SPRINKLERS
12"
min.
(305 mm)
SLAB

Anchor Clamp Installation

Installation of the anchor clamps is recommended in
all installations. Installation of the anchor clamps is
required in Florida (see Florida Building Code 301.13).
Anchor clamps hold the heat pump to the equipment
pad in order to withstand high winds caused during
extreme weather (i.e. hurricanes).
To install the anchor clamps:
1. Be sure the heat pump is in its permanent location
on the equipment pad.
2. Place the clamps at the base of the heat pump in the
four (4) locations, shown in the image to the right.
Note: Bolts and bolt anchors are not included
with the heat pump. The installer must provide
1/4" x 1-3/8" stainless steel anchor bolts and the
appropriate size concrete anchor to mount the clamp
to the equipment pad. Be sure to check local codes.
3. Fit the hook of each clamp over the lip on the base
panel of the heat pump. The hook should fit between
the lip of the base panel and the evaporator coil
guard.
2. If the heat pump is to be installed under a cover
3. Install a minimum of five (5) feet [1.52 m] from the
4. Install heat pump a minimum of 6 in. [153 mm] from
EVAPORATOR
12"
min.
(76 mm)
(305 mm)
Heat Pump Location and Clearances
Anchor
Clamps
or under a vertical overhang, the unit must have
a minimum of five (5) feet [1.52 m] clearance
from the top of the heat pump. (Manufacturer's
recommendation).
inside wall of the pool or spa unless the heat pump
is separated from the pool or spa by a five (5)
foot [1.52 m] high solid fence or other permanent
barrier. Canadian installations require a minimum
of three (3) meters [9.84 ft] from pool water.
the wall of the house.
OPEN
AIR FLOW OUT
COILS
SERVICE
ACCESS
24" min.
(610 mm)
3"
SLAB
Anchor Clamp Installation
ULTRATEMP
Heat Pump Installation and User' s Guide
®
OVER HANG
5
FT min.
(1.52 m)
"
6
min.
(153 mm)
AIR
FLOW
IN
Anchor
Clamps
3