PARAMETER DESCRIPTIONS (CONTINUED)
A3 = Alarm 1 Configuration. Determines the alarm type:
A3=0 alarm is disabled;
A3=1 alarm is activated if the temperature >=SP+A1 and deactivated if <+SP+A1-A0;
A3=2 alarm is activated if the temperature <=SP+A1 and deactivated if >+SP+A1-A0.
A4 = Alarm 2 Hysteresis. The differential associated with A5 parameter.
A5 = Alarm 2 Threshold. Number of degrees to the working set point that initiates an alarm
condition.
A6 = Alarm 2 Exclusion Time. The amount of time the alarm is disabled from instrument
activation
A7 = Alarm 2 configuration. Determines the alarm type:
A7=0 alarm is disabled;
A7=1 alarm is activated if the temperature >=SP+A5 and deactivated if <+SP+A5-A4;
A7=2 alarm is activated if the temperature <=SP+A5 and deactivated if >+SP+A5-A4.
INDICATORS
Buzzer—In the event of alarm or error condition, the internal buzzer is activated. To silence the
buzzer, press and hold the SET and DOWN keys.
LED Indications—OUT – This indicates the load is connected. The system waits for the
programmed minimum stop time of the load.
Display Messages— In normal operation, the probe temperature will be shown on the display. In
case of alarm or error, the following messages will be shown:
ER = Memory Error
= Short-Circuit Probe Error (output determined by c2)
--
oo = Open Probe Error (output determined by c2)
ACCESS TO ALL CODE PROTECTED PARAMETERS
Press SET for 8 seconds. The access code value 00 is shown on the display. (Unit comes
with code set at 00 from factory).
With the UP and DOWN arrows, set code to 118. Press SET.
Move to the desired parameter with the UP and DOWN keys.
Press SET to view the value on the display.
The value can be modified with the UP and DOWN arrows.
Press SET to enter the value and exit to text parameter.
Repeat until all necessary parameters are modified.
Press SET and DOWN at the same time to quit programming or wait one minute and the
display will automatically exit programming mode.
®
© BriskHeat
Corporation. All rights reserved.
SDC Benchtop Digital Temperature Controller
7
WARRANTY INFORMATION
BriskHeat warrants to the original purchaser of this product for the period of eighteen (18) months
from date of shipment or twelve (12) months from date of installation, whichever comes first.
BriskHeat's obligation and the exclusive remedy under this warranty shall be limited to the repair
or replacement, at BriskHeat's option, of any parts of the product which may prove defective
under prescribed use and service following BriskHeat's examination, is determined by BriskHeat
to be defective. The complete details of the warranty can be found online at
or by contacting us at 1-800-848-7673 (toll free, U.S. / Canada) or 1-614-294-3376 (Worldwide).
1055 Gibbard Ave, Columbus, OH 43201
Toll Free: 800-848-7673
Phone: 614-294-3376
Fax: 614-294-3807
®
© BriskHeat
Corporation. All rights reserved.
SDC Benchtop Digital Temperature Controller
www.briskheat.com
8