Tightening Torques - ABB ACS850-04 Guía De Instalación Rápida

Ocultar thumbs Ver también para ACS850-04:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 27
Cabling examples
ACS850-04-03A0-5...018A-5
3
ACS850-04-025A-5...094A-5
1
U1
4
3
2
V1
W1
Cable clamp on bare shield.
1
PE/Ground connection.
2
Between cable clamp and terminals, cover bare
1
3
shield with insulating tape.
Screw lug detail:
4
2
Wire sizes accepted by power
terminals
Drive type ACS850-04...
-03A0-2...08A0-2,
-03A0-5...08A0-5
-010A-2...018A-2,
-010A-5...018A-5
-025A-2...094A-2,
-025A-5...094A-5

Tightening torques

Drive type
ACS850-04...
-03A0-2...08A0-2,
-03A0-5...08A0-5
-010A-2...018A-2,
-010A-5...018A-5
-025A-2...094A-2,
-025A-5...094A-5
Drive type
ACS850-04...
-03A0-2...08A0-2,
-03A0-5...08A0-5
-010A-2...018A-2,
-010A-5...018A-5
-025A-2...050A-2,
-025A-5...050A-5
-061A-2...094A-2,
-061A-5...094A-5
Quick installation guide - ACS850-04
Wire size
0.25 ... 4 mm
0.5 ... 6 mm
6 ... 70 mm
Power terminals (supply,
motor, and braking resistor
cables)
N·m (lbf·in)
0.5 ... 0.6 (4.4 ... 5.3)
1.2 ... 1.5 (10.6 ... 13.3)
3 (25)
PE/Ground
Power cable
terminals
clamps
N·m (lbf·in)
N·m (lbf·in)
1.5 (13)
1.5 (13)
1.5 (13)
1.5 (13)
3 (25)
1.5 (13)
18 (160)
1.5 (13)
7
2
2
2
Screw lug
(Allen screw)
N·m (lbf·ft)
N/A
N/A
15 (11)
Power
connector
covers
N·m (lbf·in)
N/A
N/A
3 (25)
3 (25)