Measurement At The Neutral Terminal (E. G. Of The Generator) - Woodward MCDGV4 Traducción Del Original

Ocultar thumbs Ver también para MCDGV4:
Tabla de contenido
2 Hardware
2.8.5.3 Measurement at the Neutral Terminal (e. g. of the Generator)
2.8.5.3
Measurement at the Neutral Terminal (e. g. of the Generator)
L1
Elemento de Ejemplo
20000 V
3
After the voltage inputs have been connected correctly the residual voltage is measured
with the following setting:
• »VG[x] . Fuente VG« = «medido»
Quotient / Scaling Based on Vn
All voltage thresholds of the voltage protection modules are set in units of the nominal
voltage Vn, that is dependent on the settings »VT . TVT sec« and »VT . TVT pri«.
Example: For the voltage transformer data shown in the diagram above (secondary
voltage = 100 V / √3 ̅ ) , we have:
• »VG[x] . VG>« = 1.0⋅Vn = 100 V
Residual Voltage in Case of a 1p Ground (Earth) Fault
• VG med = Vn / √3 ̅
Example: For the voltage transformer data shown in the diagram above (secondary
voltage 100 V / √3 ̅ ) , the result is:
• VG med = Vn / √3 ̅ = 57.74 V