Module configuration
The module is configured using the DIP switch 8:
•
If DIP switch 8 is ON the module operates as a supervised
relay module.
•
If DIP switch 8 is OFF the module operates as a sounder
module.
The relay output provides only the voltage received from the
auxiliary power supply (24 VDC) – ensure that this is sufficient
for your installation.
The module will only allow sounders to be silenced from the
control panel if configured to operate as a sounder module (the
default setting).
Output connections
A maximum of 8 solenoid bells may be connected to the
supervised line. A 15 kΩ end-of-line resistor must be installed
at the end of the supervised line.
Addressing
Each module requires a numeric address between 128 and
252 for identification purposes. This is set using DIP switches
1-7. See the address table at the end of this document.
Status LED
The status LED is lit constantly during alarm.
Maintenance and testing
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
To test the module:
1.
Configure the module as an output to be activated by a
detector or manual call point.
2.
Remove a detector head from its base or activate a
manual call point.
3.
If the status LED and control panel fail to indicate the test
all connections should be checked and the module
address verified.
Specifications
Operating voltage
Loop current consumption
at 24 VDC (standby)
at 35 VDC (standby)
Alarm
Current consumption
24 VDC aux. supply (standby)*
24 VDC aux. supply (alarm)*
End-of-line resistor
Relay contact rating
Max.switching voltage
Nominal current
Operating temperature
Storage temperature
Relative humidity
Weight
Dimensions
2 / 12
22 to 38 VDC
110 µA
135 µA
<3.6 mA
6 mA
9 mA
15 kΩ
AC: 42 V peak / DC: 30 V
AC: 0.5 A / DC: 1 A
−10 to +50ºC
−10 to +70ºC
10 to 95% (non condensing)
370 g
180 × 142 × 77 mm
* Excluding loop devices
Certification and compliance
Description
Addressable Supervised Siren/Relay
Module
Certification
CPD certificate
1438-CPD-0139
Year of manufacture
The year of manufacture is included in
the first two digits of your product serial
number (located on the product
identification label).
EN54
EN54-18
EMC
EN 50130-4
EN 61000-6-3
Manufacturer
UTC Fire & Security, 129 North Main
Street, Pittsfield, Maine 04967, USA.
Manufacturer's
UTC Fire & Security B.V. Kelvinstraat 7,
representative (Europe)
6003 DH Weert, Netherlands.
ES: Instrucciónes de instalación
Descripción
El módulo KAL740 proporciona una salida de relé supervisada
para las sirenas y las válvulas de solenoide de un sistema de
detección de incendios direccionable, y supervisa la línea a la
que están conectadas.
El módulo se utiliza en los sistemas de detección que
necesitan una fuente de alimentación auxiliar de 24 VCC.
Instalación
Consulte el estándar EN54:14 y las normativas
Precaución:
locales para obtener información acerca de las directrices de
planificación, diseño, instalación, funcionamiento, utilización y
mantenimiento del sistema.
Instalación del módulo
Desconecte la fuente de alimentación del sistema de incendios
e instale el módulo en la carcasa protectora proporcionada.
Conecte el hilo apantallado del cable de bucle al tornillo de
tierra.
Una fuente de alimentación auxiliar debe proporcionar
alimentación de 24 V al módulo.
Conexión
Los conectores del módulo, el microinterruptor y el indicador
LED de estado se muestran en la Figura 1:
1.
Tornillo de tierra
2.
Conectores de bucle
3.
Conexiones de alimentación auxiliares
4.
Conectores de salida de relé
5.
Microinterruptor
6.
LED de estado
P/N 1068930 • REV 04 • ISS 01AUG14