PROBLEMS
Softener regenerates continuously
The programmer does not regenerate
automatically or when the start up button
is pushed
The programmer does not regenerate
automatically but only by pushing the start
button
Lack of softened water between two
regenerations
Failure in brine suction
An excessive quantity of brine
is fed into the tub
Salt consumption not corresponding
to what is foreseen
Intermittent or irregular brine suction
CAUSES
Fiber-optic player wrong placed
Detective camshaft
Detective timer
Power supply disconnected
Damaged or burnt out engine
Damaged or burnt out timer
Wrong timer setting
Defective printed circuit board
Hardness and capacity unset
Counting cable incorrectly inserted in the
turbine
External by pass valve open
Incorrect regeneration
Polluted resins
Wrong set up of the quantity of salt
Wrong setting of hardness or cyclic
capacity
Hardness has increased
Obstructed output
Insufficient input pressure
Output pipe blocked
Obstructed injector
Damaged injector
Valve 2 blocked in the open position
Valve line not sealed
Valve 1 remains open
The input speed has not been checked
Valve 2 remains open during suction
Air suction in the connection pipe to the tub
The brine suction pipe does not draw from
the bottom of the softener
Incorrect set up
Insufficient input pressure
Detective injector
SOLUTIONS
Place fiber-optic player in the right place
Replace the camshaft
Replace the timer
Connect
Replace engine
Replace timer
Reset the timer according to the softener
model referring to the values shown in
the column in the chart
Replace programmer
Check
Put the bayonet insert of counting cable
in the turbine section
Close the by pass valve
Repeat regeneration being sure to use
the right quantity of salt
Wash or replace resins
Check and set up again
Check and reset
Check and reset
Remove impurities to let turbine runs
without problems
Make sure there are at least 1,4 bar
Make sure the output is free
Clean injector
Replace
Remove blocking
Replace all the whole valve series
Open the valve manually to remove
impurities
Dismantle and clean the brine regulator
Open the valve manually to remove
impurities and reinforce it with a second
spring
Check the fittings and the pipe
Restore the final lower part of the
light blue pipe with bottom filter to the
softener
Reset
Make sure there are at least 1.4 bar
Replace injector