Technical features:
• PFC (passive)
• Integrated PID controller
• Control input 0-10 VDC / PWM
• Input for sensor 0-10 V or 4-20 mA
• Slave output 0-10 V max. 3 mA
• Output 20 VDC (±20 %) max. 50 mA
• Output 10 VDC (+10 %) max. 10 mA
• RS485 MODBUS
Connector Connection Assignment / function
PE
PE
Protective earth
KL1
L3
Mains; L3
L2
Mains; L2
L1
Mains; L1
KL2
NC
Status relay, floating status contact, break with error
COM
Status relay, floating status contact, changeover con-
tact, common connection (2 A, 250 V, min. 10 mA, AC1)
NO
Status relay, floating status contact, close with error
90
Electrical connections EC
L6)
• Alarm relay
• Line undervoltage / phase failure detection
• Motor current limitation
• Over-temperature protected electronics / motor
• Locked-rotor protection
• Soft start
KL3
Connector Connection Assignment / function
KL3
KL2
KL1
OUT
Master output 0-10 V max. 3 mA
GND
GND
0-10 V / PWM
Control / Actual value input (Impedance 100 k
+10 V
Supply for external potentiometer,
10 VDC (+10 %) max. 10 mA
+20 V
Supply for external sensor,
20 VDC (±20 %) max. 50 mA
4-20 mA
Control / Actual value input
0-10 V / PWM
Control / Actual value input
GND
GND
RSB
RS485 interface for MODBUS RTU; RSB
RSA
RS485 interface for MODBUS RTU; RSA
RSB
RS485 interface for MODBUS RTU; RSB
RSA
RS485 interface for MODBUS RTU; RSA
)
Ω