General information
Detail
Digital pressure monitor
Technical data
Parameters
Measuring range
Measuring tolerance
Overload protection
Medium
Supply voltage
Protection level
Relay output
Operating temperature
Display
Operation
Casing
Tube connection
Casing dimensions (L x B x H)
Order code for supply voltage 230 V, 50 Hz
Order code for supply voltage 24 V, AC / DC
Table 1: Technical data for digital pressure monitor
2
Application
»
Monitoring of differential pressure in gaseous
media, e.g. air or inert gases.
»
Measuring range from 0 to 2000 Pa.
Materials
»
Rigid ABS plastic casing.
Construction
»
Type M536AB3:
230 V AC
»
Type M536AB4:
24 V AC / DC
Equipment
»
Illuminated display with warning function;
a warning is issued when the pressure
differen tial exceeds the set limiting value.
»
Push buttons to precisely set the limiting
va lue.
»
Relay output with potential-free contact to
connect an external display device.
Value
0 ... 2000 Pa
< 5 % of the measuring range
Up to 16000 Pa
Air and inert gases
230 V/50 Hz or 24 V AC/DC
IP 40
Relay with make/break contact 250 V / 2 A
0 ... 50 °C
LCD with 124 x 64 dots
4 push buttons, protected by a membrane
2-part casing from ABS plastic
6 mm
115 x 86 x 45 mm
M536AB3
M536AB4
Digital pressure monitor - Leaflet Z/3/0/EN