Fm Installation Drawing - 5332D - PR electronics 5332 Manual Del Producto

Tabla de contenido
Idiomas disponibles

Idiomas disponibles

LERBAKKEN 10, 8410 RØNDE DENMARK.
Model 5331D, 5332D, 5333D and 5343B
Hazardous (Classified) Location
Class I,Division1, Groups, A,B,C,D T4..T6
Class I, Zone 0, AEx ia IIC T4..T6
Ambient temperature limits
T4: ‐40 to + 85 deg. Celcius
T6: ‐40 to + 60 deg. Celcius
Terminal 1 , 2
Vmax or Ui: 30 V
Imax or Ii: 120 mA
Pmax or Pi: 0.84 W
Ci: 1 nF
Li:10 uH
Terminal 3,4,5,6
Vt or Uo: 9.6 V
It or Io: 28 mA
Pt or Po: 67.2 mW
Ca or Co: 3.5 uF
La or Lo: 35 mH
Model 5335D, 5337D
Hazardous (Classified) Location
Class I,Division1, Groups, A,B,C,D T4..T6
Class I, Zone 0, AEx ia IIC T4..T6
Ambient temperature limits
T4: ‐40 to + 85 deg. Celcius
T6: ‐40 to + 60 deg. Celcius
Terminal 1 , 2
Vmax or Ui: 30 V
Imax or Ii: 120 mA
Pmax or Pi: 0.84 W
Ci: 1 nF
Li:10 uH
Terminal 3,4,5,6
Vt or Uo: 9.6 V
It or Io: 28 mA
Pt or Po: 67.2 mW
Ca or Co: 3.5 uF
La or Lo: 35 mH
Revision date:
2018-08-27
FM Installation Drawing
1
2
6
3
5
4
SENSOR
1
2
6
3
5
4
SENSOR
Version Revision
V3R0
5332V101-ES
5300Q502
WWW.PRELECTRONICS.COM
Non Hazardous Location
Associated Apparatus
or Barrier
+
with
entity Parameters:
UM < 250V
Voc or Uo < Vmax or Ui
Isc or Io < Imax or Ii
Po < Pi
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable
This device must not be connected 
to any associated apparatus which 
uses or generates more than 250 
VRMS
Non Hazardous Location
Associated Apparatus
or Barrier
+
with
entity Parameters:
UM < 250V
Voc or Uo < Vmax or Ui
Isc or Io < Imax or Ii
Po < Pi
Ca or Co > Ci + Ccable
La or Lo > Li + Lcable
This device must not be connected 
to any associated apparatus which 
uses or generates more than 250 
VRMS
Page:
1/2
15
Tabla de contenido
loading

Tabla de contenido