Siemens 3NP407 Instrucciones De Servicio página 2

Seccionador-fusible bajo carga
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 4
Fused switch disconnector
Instructions
Safety from finger-touch
To IEC 60529, DIN 40 050
Degree of protection:
Flange connection IP 00, Flange connection with connection cover IP 20
SIGUT connection IP 20
Flat/SIGUT connection with connection cover/insulating plate:
with closed grip set IP 30
with open grip set IP 20
Commissioning and maintenance by qualified persons only.
Follow the operating instructions!
WARNING:
HAZARDOUS VOLTAGE
CAN CAUSE ELECTRICAL SHOCK
AND BURNS.
DISCONNECT POWER BEFORE PROCEEDING
WITH ANY WORK ON THIS EQUIPMENT.
Application
The fuse switch disconnectors are used for closing on and disconnection of rated
operating currents up to 160 A AC.
Installation
For dimension drawings,
Fig. Ia
see
Maintain clearances to earthed components!
For permissible mounting positions, see Fig. Ib
For rear mounting, see Fig. IIa, b
For installation apertures and mounting holes, see
Fit contact carrier with 2 M5 (not hexagonal-head) screws. Always use plain and
spring washers.
Fit insulating-material block 3NY72.., see
Connection cover 3NY7101 for cable lug connection, see Fig. III.
If necessary, can be locked into position on the device at both connection sides by
pressing into guide slot.
Unlock by pressing on cover
For fitting on standard mounting rail, see Fig. IV.
3NP4075, 3NP4076
Fig. Va
For mounting on bus system, see
b
(bar thickness: 10 mm). For dismounting, see
For mounting in line between two mounting rails, see
Connection
Main conductor:
Flat connection:
Cable lug
Tightening torque
¿
2
For 2 x 70 mm
an M8 x 20 screw is required (not supplied with unit)
SIGUT terminal connection:
Single/multi-wire
Single/multi-wire
Stranded with end sleeve
Stranded with end sleeve
Stripped conductor length
Laminated copper strips, without holes up to 9 x 8 mm
Tightening torque
Terminal compartment opening for test gauge A 10 according to DIN VDE 0660 Part
100, IEC 60947-1.
Busbar adapter
: Openings at top for main conductor connection, see
Auxiliary switch
Slip-on terminal DIN 46244 - A.2.8 - 0.5
With control voltage >AC 25 V all
connections must be insulated.
Operation
Caution:
If you use an auxiliary switch (
actuated (even when the shutter is fitted) by way of the handle unit (
2
(dimensions in mm).
.
. Ensure that the surface is level!
Fig. Ic
.
Fig. IIc, d
.
(bar thickness: 5 mm) or
Fig. Vc
.
Fig. VI
.
1 x 2.5 mm² to 2 x 70 mm² ¿
10 to 12 Nm
1 x (2.5 to 70) mm²
2 x (2.5 to 16) mm²
1 x (2.5 to 50) mm²
2 x (2.5 to 10) mm²
min. 18 to max. 22 mm
8 to 10 Nm
Fig. Va, 1
Fig. VIII
), ensure that this switch is correctly
Fig. IId, e
Order No.: 3ZX1012-0NP40-2AA1
Fig. VII for fitting of the fuse links or disconnecting links
See
Use fuse links with silver-plated blades or silver-plated disconnecting links only!
Where fuse monitoring is concerned, use only fuse links with live grip links!
Fig. IIe
See
for fuse carrier installation.
Voltage test
(in the case of devices without fuse monitoring)
Use voltage test probes with diameter of ≤ 2,4 mm and minimum length of 38 mm.
The voltage is picked up at the fuse blades.
Function
Devices with fuse monitoring per 3RV1 (3NP407.-.F...), see
- U
24 ... 690 V AC (normal version), see
e
- U
24 ... 150 V DC (normal version), see
e
- U
100 ... 220 V DC (special version), see
e
Auxiliary circuit (3RV1), see
a) 1 NO + 1 NC
Plug with connecting lead (accessory 3NY1910/3NY1911)
31 NC/33 NO = blue
32 NC/34 NO = brown
Insert or pull out plug, see
Devices without fuse monitoring
≤ 150 V DC, see
- U
Fig. XIIa
e
≤ 220 V DC, see
Fig. XIIb
- U
e
Maintenance
Grease the main contacts according to switching rate (with Shell Alvania RLQ2 or
another high-grade aging-resistant mineral-oil-based lithium-soap grease/worked
penetration: 265 - 295, service temperature: -30 to +120 °C).
For replacement of the fuse line, see
Retrofitting of auxiliary switch 3NY303., see
Tightening torques of notched screws:
Technical data
Weight
without fuse monitoring
with fuse monitoring
Permissible ambient temperature
- Operation
- Storage
Operational performance
Insulation rating U
i
Rated impulse strength
Rated current I
= continuous current
th
1)
Size of fuse links
Rated conditional fused short-circuit current
at
and
Rated short-circuit making capacity with
isolating links
at
Rated thermal currents
Fuse link
Fuse switch disconnector open-type
Fuse switch disconnector enclosed
1)
Semiconductor fuse links
- used on request
The ratings for operation and of the fuses must not exceed the ratings of the
equipment.
Auxiliary switch 3NY3035, see Fig. VIII
Rated thermal current
.
Rated operational current
I
/AC-14 at 230 V, 50/60 Hz
e
Electronically compatible auxiliary switch 3NY3030, see Fig. VIII
Rated thermal current
Rated operational current
I
/AC-13 at 230 V, 50/60 Hz
e
For further data see Catalog NS K.
).
DIN VDE 0660 Part 107, IEC 60947-3
Fig. IX
Fig. IXa
Fig. IXb
Fig. IXc
Fig. X
b) 2 NO
c) 2 NC
41 NC/43 NO = black
42 NC/44 NO = white
Fig. XI
Fig. VII
.
Fig. VIII
and
Fig. VIc, 7
10 to 18 Ncm
3NP407
3NP4075
(40 mm)
0.6 kg
1.0 kg
1.2 kg
1.6 kg
-25 °C to +55 °C
-50 °C to +80 °C
2000 switching cycles
690 V
U
6 kV
imp
160 A
00
DIN 43 620, IEC 60269-2-1
I
50 kA (rms)
I
100 A/160 A
n
U
AC 500 V/AC 400 V
e
U
AC 400 V
e
I
2 kA
I
160 A
e
I
160 A
th
I
I
x
0,9
the
th
I
5 A
th
0.25 A
I
0.1 A
th
0.1 A
3NP407
English
.
.
3NP4076
(60 mm)
1.1 kg
1.7 kg

Hide quick links:

Tabla de contenido
loading

Tabla de contenido