Operation
5. Line Conditioning Setup - This option allows customization of the UPS system's
line-interactive voltage regulation capabilities. CAUTION: Improperly parameter
value setting can cause permanent damage to the unit. Changes should
only be made by qualified and trained personnel.
[0-MAIN MENU]
[5-LINE CONDITIONING SETUP]
55) Buck
Function
56) Boost Function
57) Sense Type
58) Line Qualify Time
59) High Limit [152] Vac
60) Low Limit
61) Boost Low
62) Buck High
63) High Gap
64) Low Gap
*) High back
*) Low back
*) Boost back [107] Vac
*) Buck back
>
Line Conditioning Sub-Menu Options
Buck Function (#55) - Selecting this option allows users to enable or disable
line interactive UPS overvoltage (BUCK) correction. Select ENABLE to turn on
overvoltage regulation. Select DISABLE to turn off overvoltage regulation (default =
Enabled).
[0-MAIN MENU]
[5-LINE CONDITIONING SETUP]
[55-Buck Function]
Current setting is [Enable]
0) Disable
1) Enable
>
Boost Function (#56) - Selecting this option allows users to enable or disable
line interactive UPS undervoltage (BOOST) correction. Select ENABLE to turn on
undervoltage regulation. Select DISABLE to turn off undervoltage regulation (default
= Enabled).
[0-MAIN MENU]
[5-LINE CONDITIONING SETUP]
[56-Boost Function]
Current setting is [Enable]
0) Disable
1) Enable
>
[088] Vac
[102] Vac
[128] Vac
[005] Vac
[005] Vac
[147] Vac
[093] Vac
[123] Vac
39