EZ Alarm Installation Instructions
®
This alarm system monitors liquid levels in lift pump chambers, sump pump basins, holding
tanks, sewage, agricultural, and other water applications.
The Tank Alert
EZ indoor/outdoor alarm can serve as a high or low level alarm depending on the
®
float switch model used. This easy-to install alarm features an innovative, sleek 2-color molded
enclosure which integrates the LED red translucent beacon. The alarm sounds and the upper
half of the housing illuminates when a potentially threatening liquid level condition occurs. The
audible alarm can be silenced by pressing the Test/Silence button, but the alarm light will remain
on until the condition is remedied. Once the condition is cleared, the alarm will automatically reset.
A green "power on" light indicates power to the alarm panel.
TANK ALERT
EZ ALARM
®
120 VAC Model - (circuits not supervised) Primary: 120 VAC, 50/60 Hz, 3.8 watts max.
(alarm condition) Operating Voltage: 9 VDC
240 VAC Model - (circuits not supervised) Primary: 240 VAC, 50/60 Hz, 3.8 watts max.
(alarm condition) Operating Voltage: 9 VDC
Enclosure meets Type 3R water-tight standard.
External mounting tabs for easy installation.
Integrated LED beacon illuminates upper translucent half of enclosure.
Removable lower cover allows greater access for easier field wiring while the internal
circuitry remains protected.
Interlocking enclosure has a unique sound chamber to amplify the horn while preventing
moisture from entering.
Automatic alarm reset, horn silence switch, and alarm test switch.
Alarm horn sounds at 82 decibels at 10 feet (3 meters)
Alarm system (when installed on separate circuit) operates even if pump circuit fails.
Includes auxiliary alarm contacts for easy attachment of remote devices: (circuit not
supervised) 240 VAC/30 VDC, 1.5 amps max., 50/60 Hz.
Complete package includes standard SJE SignalMaster
(4.57 meters) of cable (other lengths available) and mounting clamp.
Three-year limited warranty.
Patents Pending
OPTIONS
When ordered with the alarm, the system is available with:
alternate float switch models for high or low level warning.
premounted terminal block so enclosure can also be used as a junction box for splicing
pump, pump switch, and pump power. Meets NEC standard for junction boxes. 20 Amps,
120/240 VAC.
6 foot (1.8 meter) power cord with 120 VAC plug and liquid tight connector. (120 VAC
model only)
PREVENTATIVE MAINTENANCE
• Periodically inspect the product. Check that the cable has not become worn or that the housing
has not been damaged so as to impair the protection of the product. Replace the product
immediately if any damage is found or suspected.
• Periodically check to see that the float is free to move and operate the switch.
• Use only SJE-Rhombus
replacement parts.
®
control switch with 15 feet
®
ELECTRICAL SHOCK HAZARD
Disconnect power before installing or servicing
this product. A qualified service person must
install and service this product according to
applicable electrical and plumbing codes.
Failure to follow these precautions could result in serious injury or death. Replace product immediately if
switch cable becomes damaged or severed. Keep these instructions with warranty after installation.
This product must be installed in accordance with National Electric Code, ANSI/NFPA 70 so as to prevent
moisture from entering or accumulating within boxes, conduit bodies, fittings, float housing, or cable.
For detailed specifications on this product, or for the complete line of SJE-Rhombus
panel, alarm, and switch products, visit our web site at www.sjerhombus.com.
INSTALLING THE FLOAT SWITCH
1.
Place the cord into the clamp as shown in Figure A.
2.
Locate the clamp at the desired activation level and secure the clamp to the discharge pipe
as shown in see Figure A. Note: Do not install cord under hose clamp.
3.
Tighten the hose clamp using a screwdriver. Over tightening may result in damage to the
plastic clamp. Make sure the float cable is not allowed to touch the excess hose clamp
band during operation.
4.
Wire cable leads directly into control device as shown in Figure B.
5.
Check installation. Allow system to cycle to insure proper operation. Note: All hose clamp
components are made of 18-8 stainless steel material. See your SJE-Rhombus
for replacements.
INSTALLING THE ALARM
1. Mount alarm box using existing upper and lower mounting tabs on the exterior of the
enclosure. Note: Screws are to be located over wall stud or used with a wall anchor sized
for the #8 x 1.25" self-tapping screw.
2. Remove screw from front of lower cover.
3. Lift bottom of lower cover out slightly, as shown in Figure C.
4. Slide lower cover down until it is clear of the upper cover and remove, as shown in Figure C.
5. Determine "conduit-in" location on alarm as shown in Figure B. See bottom of enclosure for
cord placement indicator marks. Note: When used with a pump application, connect alarm
to a circuit separate from the pump circuit. This allows the alarm to continue to operate if the
pump circuit fails.
6. Drill holes for conduit entry, taking care not to damage any interior features or components.
7. Attach conduit. Note: Be sure conduit entrances in to the enclosure are properly sealed.
If alarm included the pre-mounted terminal block option,
refer now to the Terminal Block Option Wiring Instructions.
8. Bring alarm float switch cable through conduit and wire to terminal block positions marked
"FLOAT SWITCH" on the circuit board, as shown in Figure B.
9. Wire power conductors to terminal block positions marked "L1 and L2/N on circuit board, as
shown in Figure B.
10. Place ground wire under screw in ground termination post as shown in Figure B. Note: If
terminal block option is used, attach ground wire as shown in Figure A of Terminal Block
Option Wiring Instructions.
11. If remote device is used, connect wires to appropriate terminal block positions labeled "N/O,
COMMON, N/C" on circuit board as shown in Figure B.
12. Replace lower cover onto alarm, reversing steps 2-4. Be sure the lower cover is fully seated
prior to reinstalling the lower cover screw. Caution: Do on over torque the screw. Screw
boss may be damaged if over-tightened.
13. Turn on power to the alarm. The green "Power ON" indicator will turn on.
14. Check installation by manually tipping the float. The horn and beacon will turn on.
15. Push the "Test/Silence" button to test the silence feature.
16. Important: Test unit once per week to insure proper operation.
22650 County Highway 6  P.O. Box 1708  Detroit Lakes, Minnesota 56502 USA
1-888-DIAL-SJE (1-888-342-5753)  Phone: 218-847-1317  Fax: 218-847-4617
EXPLOSION OR FIRE HAZARD
Do not use this product with flammable
liquids. Do not install in hazardous
locations as defined by National
Electrical Code, ANSI/NFPA 70.
®
supplier
®
Instl. Instr. PN 1036543A
©SJE-Rhombus
03/13
loading

Resumen de contenidos para SJE Rhombus TANK ALERT EZ

  • Página 1 ELECTRICAL SHOCK HAZARD EXPLOSION OR FIRE HAZARD Disconnect power before installing or servicing Do not use this product with flammable this product. A qualified service person must liquids. Do not install in hazardous install and service this product according to locations as defined by National TANK ALERT EZ Alarm Installation Instructions...
  • Página 2 RIESGO DE CHOQUE ELÉCTRICO RIESGO DE INCENDIO O EXPLOSIÓN Desconecte el cable de alimentación antes No utilice este producto con líquidos de instalar este producto o de hacerle inflamables. mantenimiento. La instalación y el mantenimiento No lo instale en lugares peligrosos definidos de este producto deben ser efectuados por como tales en el Código Eléctrico Nacional Instrucciones de instalación de la alarma TANK ALERT...
  • Página 3 RISQUE DE CHOC ÉLECTRIQUE RISQUE D’INCENDIE OU D’EXPLOSION AVERTISSEMENT AVERTISSEMENT Débrancher l’alimentation avant d’installer ou Ne pas utiliser ce produit avec des liquides d’entretenir ce produit. Seule une personne inflammables. qualifiée est habilitée à installer et entretenir Ne pas installer ce produit dans des sites Instructions d’installation de l’alarme TANK ALERT ®...
  • Página 4 FIGURES/FIGURAS/FIGURES SJE-RHOMBUS ® THREE-YEAR LIMITED WARRANTY SJE-RHOMBUS warrants to the original consumer that this product shall be free of manufacturing defects for three years ® Figure A/Figura A Figure C/Figura C after the date of consumer purchase. During that time period and subject to the conditions set forth below, SJE-RHOMBUS ®...

Este manual también es adecuado para:

Sje-a1036594