Troubleshooting
13 Troubleshooting
13.1 Proceed as follows for troubleshooting
Even if you are in a rush, proceed systematically and in a targeted manner.
In the worst case, arbitrary, indiscriminate disassembly and modifications to the settings may
mean that you are no longer able to determine the original cause of the error.
Get an overview of the function of the product as related to the overall system.
Try to clarify whether the product fulfilled the required function in the overall system before
the error occurred.
Try to detect all changes to the overall system in which the product is installed:
– Have the conditions or application for the product changed?
– Have changes (e.g. conversions) or repairs been made to the overall system (machine/system,
electrical, controller) or the product? If yes, which ones?
– Has the product or machine been operated as intended?
– What kind of malfunction has occurred?
Try to get a clear picture of the cause of the error. If necessary, ask the immediate machine
operator or foreman.
13.2 Table of malfunctions
Table 30 contains an overview of malfunctions, possible causes, and remedies.
If you cannot remedy a malfunction, please contact AVENTICS GmbH. The address is printed on
the back cover of these instructions.
Table 30:
Table of malfunctions
Malfunction
No outlet pressure at the valves
Outlet pressure too low
Air is audibly escaping
Possible cause
No power supply on the bus
coupler or the electrical supply
plate
(see also the behavior of the
individual LEDs at the end of the
table)
No set point stipulated
No supply pressure available
Supply pressure too low
Insufficient power supply
for the device
Leaks between the valve system
and connected pressure line
Pneumatic connections confused
Remedy
Connect the power supply at plug
X1S on the bus coupler and to
the electrical supply plate.
Check the polarization of the
power supply on the bus coupler
and the electrical supply plate.
Switch on system component.
Stipulate a set point.
Connect the supply pressure.
Increase the supply pressure.
Check LEDs UA and UL on the bus
coupler and the electrical supply
plate and supply the devices with
the correct (adequate) voltage.
Check the pressure line
connections and tighten,
if necessary.
Connect the pneumatics for
the pressure lines correctly.