After-Sales Service And Warranty; 11.1. After-Sales Service; Shortening Of "Maintenance Cycle" And "Replacement Cycle" Needs To Be Considered In Following Situations - Daikin CMSQ200A7W1B Manual De Operación

Ocultar thumbs Ver también para CMSQ200A7W1B:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 33
11. A
-
FTER
SALES SERVICE AND WARRANTY
Warranty period
This product includes a warranty card that was filled out by the
dealer at the time of installation. The completed card was
checked by the customer and stored carefully.
If repairs to the air conditioner are necessary within the warranty
period, contact your dealer and keep the warranty card at hand.

11.1. After-sales service

Recommendations for maintenance and inspection
Since dust collects when using the unit for several years,
performance of the unit will deteriorate to some extent.
As taking apart and cleaning interiors of units requires technical
expertise and in order to ensure the best possible maintenance
of your units, we recommend to enter into a maintenance and
inspection contract on top of normal maintenance activities.
Our network of dealers has access to a permanent stock of
essential components in order to keep your air conditioner in
operation as long as possible.
Contact your dealer for more information.
When asking your dealer for an intervention, always state:
the complete model name of the air conditioner
the manufacturing number (stated on the nameplate of the
unit)
the installation date
the symptoms or malfunction, and details of the defect.
WARNING
Do not modify, disassemble, remove, reinstall or
repair the unit yourself as incorrect dismantling or
installation may cause an electric shock or fire.
Contact your dealer.
In case of accidental refrigerant leaks, make sure
there are no naked flames. The refrigerant itself is
entirely safe, non-toxic and non-combustible, but it will
generate toxic gas when it accidentally leaks into a
room where combustible air from fan heaters, gas
cookers, etc. ... is present.
Always have qualified service personnel confirm that
the point of leakage has been repaired or corrected
before resuming operation.
Recommended inspection and maintenance cycles
Be aware that the mentioned maintenance and replacement cycles
do not relate to the warranty period of the components.
Table 1: "Inspection Cycle" and "Maintenance Cycle" list
Component
Electric motor
PCB
Heat exchanger
Sensor (thermistor, etc.)
Remote controller and switches
Drain pan
Expansion valve
Electromagnetic valve
Table 1 assumes the following conditions of use:
1.
Normal use without frequent starting and stopping of the unit.
Depending on the model, we recommend not starting and
stopping the machine more than 6 times/hour.
2.
Operation of the unit is assumed to be 10 hours/day and 2,500
hours/year.
CMSQ200+250A7W1B
Air conditioning system
4PW47628-1
Maintenance cycle
(replacements and/
Inspection cycle
or repairs)
20,000 hours
25,000 hours
5 years
5 years
1 year
25,000 hours
8 years
20,000 hours
20,000 hours
NOTE
1.
Table 1 indicates main components.
Refer to your maintenance and inspection contract
for more details.
2.
Table 1 indicates recommended intervals of
maintenance cycles. However, in order to keep the
unit operational as long as possible, maintenance
work may be required sooner.
Recommended
appropriate maintenance design in terms of
budgetting maintenance and inspection fees.
Depending on the content of the maintenance and
inspection contract, inspection and maintenance
cycles may in reality be shorter than listed.
11.2. Shortening of "maintenance cycle" and
"replacement cycle" needs to be considered in
following situations
The unit is used in locations where:
1.
heat and humidity fluctuate out of the ordinary
2.
power fluctuation is high (voltage, frequency, wave distortion,
etc.)
(The unit cannot be used if power fluctuation is outside the
allowable range.)
3.
bumps and vibrations are frequent
4.
dust, salt, harmful gas or oil mist such as sulfurous acid and
hydrogen sulfide may be present in the air
5.
the machine is started and stopped frequently or operation time
is long (sites with 24 hour air-conditioning).
Recommended replacement cycle of wear parts
Table 2: "Replacement Cycle" list
Component
Air filter
High efficiency filter (Optional)
Fuse
Crankcase heater
1.
Table 2 indicates main components.
NOTE
Refer to your maintenance and inspection contract
for more details.
2.
Table 2 indicates recommended intervals of
replacement cycles. However, in order to keep the
unit operational as long as possible, maintenance
work may be required sooner.
Recommended
appropriate maintenance design in terms of
budgetting maintenance and inspection fees.
Contact your dealer for details.
Damage due to taking apart or cleaning interiors of
NOTE
units by anyone other than our authorised dealers may
not be included in the warranty.
Moving and discarding the unit
Contact your dealer for removing and reinstalling the total
unit. Moving units requires technical expertise.
This unit uses hydrofluorocarbon.
Contact your dealer when discarding this unit. It is required
by law to collect, transport and discard the refrigerant in
accordance with the "hydrofluorocarbon collection and
destruction" regulations.
intervals
can
be
used
Maintenance cycle
(replacements and/
Inspection cycle
or repairs)
5 years
1 year
1 year
10 years
8 years
intervals
can
be
used
Operation manual
for
for
7
Tabla de contenido
loading

Este manual también es adecuado para:

Cmsq250a7w1b

Tabla de contenido