4. Saving Parameters
Here in this menu, the installer can enter and save new parameters for Comelit series addressable
detectors: 41RCS000, 41RFU000, 41RML000.
The programming options are: changing the address of the detector and setting of new parameters for
day and night alarm levels.
ATTENTION: To ensure correct parameters setting, it is obligatory first to read the current set
parameters and then to enter the "Save parameters" menu!
To configure new parameters for a detector:
Press the
you have entered other menus earlier.
Mount the detector to the programmer's base.
Enter "Read parameters" menu and review the set parameters. Exit to the main menu.
Use the
Set address
Check address
Read parameters
Save parameters
Press the
The blinking arrow "" pointing to the left, means that the programmer is saving (writing)
parameters to the detector. On the same row is displayed the type of the detector.
Configuration and saving of parameters. Use the
different parameters.
Address – Shows the current address of the detector.
o
To enter new address, press the
settings mode – the last digit of the address is blinking. Follow the same procedure
described in "Set address" menu. Confirm the new entered address with
button. Press the
Day level – Shows the current set day alarm level - for the heat detectors the class
o
according EN-54, and for the optical-smoke detectors – the level of sensitivity of the
smoke chamber according EN-54.
To enter new Day level, press the
settings mode – the edited parameter is blinking. Press the
you reach the desired class or sensitivity level. Confirm the new entered parameter
with
o
Night level - Shows the current set night alarm level - for the heat detectors the class
according EN-54, and for the optical-smoke detectors – the level of sensitivity of the
smoke chamber according EN-54.
To enter new Night level, press the
settings mode – the edited parameter is blinking. Press the
you reach the desired class or sensitivity level. Confirm the new entered parameter
with
Save – Saving of the new set address and/ or parameters to the detector. Press the
o
message "Successfully" means that the new address and/ or parameters are
successfully configured to the detector.
(Esc) button several times to exit back to the main programming menu in case
(Down) buttons to choose the "Save parameters" menu:
(Up) and
(Enter) button.
(Down) button to move to the next parameter.
(Enter) button. Press the
(Enter) button. Press the
(Enter) button to start. For a while the message "Wait, please..." is displayed. The
41SPG000 – Instruction Manual
(Up) and
(Down) to scroll over the
(Enter) button. The programmer enters in
(Enter) button. The programmer enters in
(Down) button to move to the next parameter.
(Enter) button. The programmer enters in
(Down) button to move to the next parameter.
(Enter)
(Down) button until
(Down) button until
14