Comelit 41SPG000 Manual Tecnico página 13

Caja de conexión bullet analógico start
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

3. Reading Parameters
Here in this menu, the installer can review the set parameters of Comelit series addressable detectors:
41RCS000, 41RFU000, 41RML000. The parameters differ according the type of the detector. The
parameters available for reading are listed in the table below:
41RSC000
Address
Day alarm level: Class*
Night alarm level: Class*
CONFIG
Version
* Class according EN54-5: A1R/ A2S/ BS
** Sensitivity level according EN54-7: Low/ Middle/ Normal/ High
Note: At detector 41RML000 the class A1R is factory set for the heat part and could not be changed.
To view the set parameters of a detector:
Press the
you have entered other menus earlier.
Mount the detector to the programmer's base.
Use the
Set address
Check address
Read parameters
Save parameters
(Enter) button. The message "Read parameters. Wait, please..." is on the screen
Press
while reading the detector parameters, and after that is displayed the type of the detector and
the respective parameters accessible for viewing.
The blinking arrow "" pointing to the right, means that the programmer is reading
parameters. On the same row is displayed the type of the detector.
The parameters differ according the type of the detector:
o
o
o
o
o
Example: Setting the parameters for 41RCS000.
Set address
Check address
Read parameters
Save parameters
Note: To review all parameters of 41RFU000 and 41RML000 use the
more time.
41RFU000
Address
Day alarm level: Sensitivity**
Night alarm level: Sensitivity **
OPTOFFSET
OPTGAIN
CALIBRATION
CONFIG
Version
(Esc) button several times to exit back to the main programming menu in case
(Down) buttons to choose the "Read parameters" menu:
(Up) and
Address – Shows the current address of the detector.
Day – Shows the current set day alarm level - for the heat detectors the class
according EN-54, and for the optical-smoke detectors – the level of sensitivity of
the smoke chamber according EN-54.
Night - Shows the current set night alarm level - for the heat detectors the class
according EN-54, and for the optical-smoke detectors – the level of sensitivity of
the smoke chamber according EN-54.
OPTOFFSET, OPTGAIN, CALIBRATION, CONGIF – specialized parameters
configured from the manufacturer.
Version – Shows the current software revision.
▌
Address
Day
Night
41SPG000 – Instruction Manual
41RML000
Address
Day alarm level: Sensitivity **
Night alarm level: Sensitivity **
OPTOFFSET
OPTGAIN
CALIBRATION
CONFIG
Version
41RCS000
1
A1R
A1R
▌
41RCS000
CONFIG 4
Version
1.0
(Down) button one
13
Tabla de contenido
loading

Tabla de contenido