Octo-input Interface Module with Relay
4
Technical specifications
The module provides line monitoring with EOL or contact monitoring. (1.6)
LSN input voltage (V DC)
Max. current consumption from LSN (mA)
Inputs, independent
Line monitoring: EOL resistor, nominal (kΩ)
Detected line conditions (Ω) with overall line resistance R
Contact monitoring: Max. current consumption (mA)
Min. activation time of the inputs IN 1...8 (s)
Change-over relay, low voltage
Contact load: Max. switching capacity (A / V DC; A / V AC)
Min. switching capacity (mA / mV DC; mA / mV AC)
Max. frequency (Hz)
Dimensions W x H x D (mm)
2
Wire gauge (mm
)
Housing material, housing color (RAL)
Operating temperature (°C)
Storage temperature (°C)
Rel. humidity (%), non-condensing
Class of equipment (IEC 60950)
Degree of protection (IEC 60529)
Bosch Sicherheitssysteme GmbH
 = R
 + R
 + R
Σ
L/1
L/2
Installation Guide
Technical specifications | en
15 ... 33
5.5
8
3.9
Standby: 1500 ... 6000
EOL
Interruption: > 12000
Short circuit: < 800
8
3.2
NC / COM, COM / NO
2 / 30; 0.5 / 42.4
0.01 / 10; 0.01 / 10
100
140 x 200 x 48
0.6...3.3
ABS+PC-FR, RAL 9003
-20 ...+65
-25 ...+80
< 96 %
III
IP 54
2016.01 | 5.0 | F.01U.032.847