All parameters which are expressed as percentage values (ON/OFF
hysteresis, proportional band) also refer to this scale.
3
Auxiliary output A1:
Operating of second relay.
0
Disabled
1
Set the status of the relay at end of cycle
2
Set the status of relay for each segment of the cycle
3
Same operating of both relays for maximum power
4
General alarm (relay N.O.)
5
Band alarm (relay N.O.)
6
Upper deviation alarm (relay N.O.)
7
Lower deviation alarm (relay N.O.)
8
Set the status of relay during the cycle (N.O. at Start and Stop,
Closed during the cycle)
9
General alarm (relay N.C.)
10
Band alarm (relay N.C.)
11
Upper deviation alarm (N.C.)
12
Lower deviation alarm (N.C.)
13
Set the status of relay during the cycle (N.C. at Start and Stop,
Open during the cycle)
14
Control of safety contactor
5
Off set correction for sensor input (-150/150 °C or °F):
6
Gain calibration for sensor input (-5.0%...+5.0%):
These parameters act to adjust eventual mistakes caused by damages or
errors on thermocouple wiring and to set the precision of thermocouple
on a well defi nite point of the scale. If a pyrometric cone for kilns
melts at 1000°C but controller shows 990°C, it is enough to enter 1.0
on P-06 to correct visualization.
7
Proportional band (0-1800 °C or °F)
8
Integral time (0/9999 sec). ( Zero excludes integral)
9
Derivative time (0.0/999.9 sec). (Zero excludes derivative)
10
Cycle time for output with proportional time (1/120 sec):
GB