LPG kit
2.1

Kit description

The kit allows the burners designed to work with natural gas to
burn LPG. The kit is composed of:
Description
Distributor assembly
Central tube
Label
Instruction
2.2

Technical features

Burner
Max. burner output
Min. burner output
Minimum gas
pressure
Fuel
2.3
Conversion
Proceed as follows:
Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
 Remove the electrodes by first removing the fixing plates.
Take care not to break the ceramics.
 Remove the fixing/adjustment plates from the central pipe.
 Replace the gas distributor with the one supplied in the kit,
paying attention to the two holes for the electrodes.
 Insert the central pipe supplied in the kit, then replace the
fixing plates and adjust them according to the burner instruc-
tions (the same adjustment as for methane).
 Replace the electrodes, positioning them as shown in the kit
instructions.
Adjust the electrode and the probe as indicated in
Fig. 2.
WARNING
20023573
Quantity
1
1
1
1
RS 70 - RS 70/M
RS 70/E
465 - 814 kW
400 - 700 Mcal/h
192 kW
165 Mcal/h
In order to have the maximum burner output, it is necessary:
26.5 mbar
measured at the pipe coupling, with combustion chamber at 0 mbar and gas with Net calorific value =
3
22,200 kcal/m
Commercial LPG (C
H
= 93 - 94%)
3
8
Net calorific value = 25.8 kWh/Nm
LPG kit
Apply the self-adhesive label for LPG operation
near the characteristics label.
WARNING
Before starting the kit installation operations, get a
suitable lifting system ready.
Be careful as some drops of fuel may leak out dur-
ing the kit installation phase.
RS 100 - RS 100/M
RS 130 - RS 130/M
RS 100/E
698 - 1163 kW
600 - 1000 Mcal/h
232 kW
200 Mcal/h
31 mbar
3
3
- 22.200 kcal/Nm
D1257
D613
2
GB
RS 150 - RS 150/M
RS 130/E
930 - 1512 kW
800 - 1300 Mcal/h
774 - 1591 Mcal/h
232 kW
200 Mcal/h
17.4 mbar
900 - 1850 kW
372 kW
320 Mcal/h
24.1 mbar
Fig. 1
Fig. 2