2
LPG kit
2.1
Kit description
The kit allows the burners designed to work with natural gas to
burn LPG. The kit is composed of:
Description
Distributor assembly
Central tube
Label
Instruction
2.2
Technical features
Burner
Max. burner output
Min. burner output
Minimum gas
pressure
Fuel
2.3
Conversion
Proceed as follows:
Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
Remove the electrodes by first removing the fixing plates.
Take care not to break the ceramics.
Remove the fixing/adjustment plates from the central pipe.
Replace the gas distributor with the one supplied in the kit,
paying attention to the two holes for the electrodes.
Insert the central pipe supplied in the kit, then replace the
fixing plates and adjust them according to the burner instruc-
tions (the same adjustment as for methane).
Replace the electrodes, positioning them as shown in the kit
instructions.
Adjust the electrode and the probe as indicated in
Fig. 2.
WARNING
20023573
Quantity
1
1
1
1
RS 70 - RS 70/M
RS 70/E
465 - 814 kW
400 - 700 Mcal/h
192 kW
165 Mcal/h
In order to have the maximum burner output, it is necessary:
26.5 mbar
measured at the pipe coupling, with combustion chamber at 0 mbar and gas with Net calorific value =
3
22,200 kcal/m
Commercial LPG (C
H
= 93 - 94%)
3
8
Net calorific value = 25.8 kWh/Nm
LPG kit
Apply the self-adhesive label for LPG operation
near the characteristics label.
WARNING
Before starting the kit installation operations, get a
suitable lifting system ready.
Be careful as some drops of fuel may leak out dur-
ing the kit installation phase.
RS 100 - RS 100/M
RS 130 - RS 130/M
RS 100/E
698 - 1163 kW
600 - 1000 Mcal/h
232 kW
200 Mcal/h
31 mbar
3
3
- 22.200 kcal/Nm
D1257
D613
2
GB
RS 150 - RS 150/M
RS 130/E
930 - 1512 kW
800 - 1300 Mcal/h
774 - 1591 Mcal/h
232 kW
200 Mcal/h
17.4 mbar
900 - 1850 kW
372 kW
320 Mcal/h
24.1 mbar
Fig. 1
Fig. 2