TROUBLESHOOTING
PROBLEM
Short runtime in Battery mode
ALARMS
Output Overload
Battery failure
Batteries disconnected
EPO active
Over Temperature
FAN Failure
EEPROM Failure
ERROR CODES
01 , 02 , 03, 04, 11, 12, 13
14
21
41
43
IMPORTANT: In case of extreme failure or when burning smell is detected, UPS input lines must be powered off
immediately and UPS must be turned-off by <OFF> button. Wait until LCD turns-off. Then call technical service.
USER MANUAL - OPTIMA T09W 6K/10K
PROBABLE CAUSE & SOLUCION
Low Batteries Charge: Recharge Batteries during 4-6 h.
Old Batteries: Batteries must be replaced by new ones
PROBABLE CAUSE & SOLUCION
High power consumption connected to UPS: Disconnect no critical
equipment from UPS.
If UPS is blocked by overload alarm, solve overload cause and unblock
UPS as described in ALARMS section of this manual.
Batteries are disconnected or with a very low charging level:
Revise batteries connection.
Recharge batteries during 4-6 hours.
If problem is not solved call technical service.
Revise batteries connection.
Revise EPO port on rear panel of UPS. If external switch is connected to
EPO port, check external switch.
Check if fans are working properly.
Check if room temperature is in acceptable range.
Disconnect non critical equipment from UPS to reduce internal
temperature.
If problem is not solved call technical support.
Check if fans are working properly. If not call technical service.
Turn-off and power-off UPS.
Restart UPS. If not solved call technical service.
PROBABLE CAUSE & SOLUCION
- Turn-off and power-off UPS. Disconnect all equipment connected to
UPS.
- Restart UPS with no loads connected to its output.
- If UPS starts-up without problems, find faulty equipment and remove it
from UPS.
If problem is not solved call technical support.
- Short circuit detected in UPS output.
- Disconnect all equipment connected to UPS.
- Power UPS off and restart it.
Find faulty load to remove it from UPS.
- Power UPS off. Disconnect all loads from the UPS.
- Check Battery voltage and verify a proper connection between UPS and
external batteries.
If problem is not solved call technical support.
Power UPS off. Check room temperature. If it is high, solve room
temperature before restarting UPS.
UPS overload detected. Power off UPS to remove some non-critical
loads. Then restart UPS.
VER.1801.25-WP+ (ENG)