UPS INSTALLATION ON SITE
Place UPS on plane floor in a site with environmental conditions required in this manual. It is mandatory to keep free room between UPS
and close objects:
EXTERNAL BATTERY CABINETS (XBAT) – CONNECTION PROCEDURE
External batteries must be connected to UPS by using original XMART DC cable provided inside the box,
IMPORTANT: All OPTIMA RT 6K and 10K work with 240VDC battery voltage. This voltage is provided by battery packs by
connecting 20 batteries 12VDC in series. There could be some UPS models working with a different DC voltage. User
must check carefully XBAT voltage is compatible with the UPS DC voltage before making DC connections.
In case electrical information given by this manual does match with information provided by product labels, user must
consider information on labels or printed on the product.
1)
Place UPS module close to original XMART XBAT modules.
2)
Check all DC switches on XBAT are in OFF state.
3)
Connect UPS to first XBAT module by using original DC cable
4)
In case system has more than 1 XBAT, connect XBAT#1 to XBAT#2. Then XBAT# 2 to XBAT#3 and so on.
USER MANUAL - OPTIMA T09W 6K/10K
VER.1801.25-WP+ (ENG)
9