9. ALARM & ERROR CODES / TROUBLESHOOTING
IMPORTANT:
All alarm and errors are informed don the LCD by dedicated codes and symbols.
▪
ALARMS: Are usually represented by blinking codes or symbols. Audible alarm beeps are also intermittent for alarms. Alarm
▪
states do not avoid UPS working in ONLINE mode.
ERRORS: Are usually represented by steady codes or symbols. Audible alarm for errors always sounds continuously. Error
▪
states force UPS to go to Static Internal BYPASS mode.
ALARM SYMBOLS AND CODES
ALARM
OVERLOAD detected at UPS output
LOW BATTERY
BATTERY DISCONNECTED OR FAULTY
BATTERY OVER-VOLTAGE
INPUT FUSES BROKEN
EMERGENCY POWER-OFF ACTIVATED
HIGH TEMPERATURE
CHARGER FAILURE
* UPS BLOCKED: as consequence of detecting 3 overloads
in less than 30 minutes OR
* MBS cover REMOVED
ALARMS
Battery Disconnected
Battery overvoltage
Los Battery
Overload at UPS output
FAN failure
EPO activated
Over temperature
Charger failure
Internal input fuse broken
Configuration mismatch in ONLINE for parallel (available only for UPS with parallel functionality)
Configuration mismatch in BYPASS for parallel (available only for UPS with parallel functionality)
UPS blocked by 3 consecutives overloads (in less than 30 minutes)
MBS safety plate removed
Input BYPASS unstable
Boot Loader failure
Some errors and alarms could block UPS until problem is solved and UPS unblocked by operator. Operator must be
sure cause of problem has been solved before clear alarm and unblock UPS. Alarm can be deleted by pressing
<UP> and <DOWN> keys at same time, when UPS is in BYPASS mode.
USER MANUAL - OPTIMA T09W 6K/10K
ALARM SYMBOLS
VER.1801.25-WP+ (ENG)
AUDIBLE BEEP
2 beep / s
1 beep / s
1 beep / s
1 beep / s
1 beep / s
1 beep / s
1 beep / s
1 beep / s
1 beep / s
ALARM CODES
01
07
08
09
0A
0B
0D
0E
10
21
22
33
3A
3D
3E
25