Lenze L−force EZS3 A200 Serie Instructions De Montage página 49

Ocultar thumbs Ver también para L−force EZS3 A200 Serie:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

How to connect the filter:
1. Loosen three screws 0 and remove the terminal cover 1
2. Connect filter input cable to terminals 1U1, 1V1, 1W1 and PE.
Connect filter output cable to terminals 1U2, 1V2, 1W2 and PE.
– Observe tightening torques!
– The PE connection must comply with EN 61800−5−1.
3. The shield must be connected with a large surface to the shield sheet (PES).
– Turn down the shield and use metal cable binders to fix it (not included in the
scope of supply, e.g. EZAMBKBM) 2.
– Alternative: Insert shield mounting kit EZAMBHXMxxx (not included in the scope
of supply) and mount cable binders in addition for strain relief 3.
4. Insert terminal cover 1 and fix it with three screws 0.
{
Danger!
Hazardous electrical voltage
The terminal cover 1 serves to protect persons!
If the filter is operated without a terminal cover 1, it is possible to touch live
parts at the terminals. These parts remain live for up to three minutes after
mains disconnection.
Possible consequences:
Death or severe injuries.
ƒ
Protective measures:
Only commission the filter if the terminal cover is mounted.
ƒ
Switch off the power supply and wait for at least three minutes before
ƒ
dismounting the terminal cover. Ensure that all terminals are in a
de−energised state.
EDKZS3X200 DE/EN/FR/ES/IT 4.0
Electrical installation
l
Mounting steps
6
49
Tabla de contenido
loading

Tabla de contenido