Type
Mounting
Mounting position
Minimum distance to other units, horizontal/vertical
Degree of protection
Material of enclosure
Protection class ( EN 61140)
Electrical connection - Input side
Wire size
fine-strand with wire end ferrule
fine-strand without wire end ferrule
Stripping length
Tightening torque
Electrical connection - Output side
Wire size
fine-strand with wire end ferrule
fine-strand without wire end ferrule
Stripping length
Tightening torque
Environmental data
Ambient temperature range
Damp heat (IEC/EN 60068-2-3)
Climatic category (IEC/EN 60721-3-3)
Isolation data
Rated impulse withstand voltage
U imp between all isolated circuits
(IEC/EN 60950-1, EN 50178)
Pollution degree (IEC/EN 60950, EN 50178)
Standards
Product standard
Low Voltage Directive
EMC Directive
Electrical safety
Protective low voltage
Electromagnetic compatibility
Interference immunity to
electrostatic discharge
radiated, radio-frequency, electro magnetic field
electrical fast transient / burst
surge
conducted disturbances, induced by radio-
frequency fields
Interference emission
high-frequency radiated
high-frequency conducted
Additional information relating to UL approvals:
Power, input and output (I/O) wiring must be in accordance with Class I, Div. 2 wiring methods - Article 501-10(B) (1)
of the National Electrical Code.
- SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C, D OR NON-HAZARDOUS LOCATIONS ONLY.
- WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2.
- WARNING - EXPLOSION HAZARD - DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS
KNOWN TO BE NON-HAZARDOUS.
enclosure / terminals
enclosure shell / cover
pluggable connecting terminals, actuate only when power off
rigid
pluggable connecting terminals, actuate only when power off
rigid
operation
full load
storage
input / output
input / PE
output / PE
CP-S 24/5.0
CP-S 24/10.0
DIN rail (IEC/EN 60715), snap-on mounting
10 mm / 80 mm (0.39 in / 3.15 in)
aluminium / zinc-coated sheet steel
2
0.2-2.5 mm
/ 24-14 AWG
2
0.2-2.5 mm
/ 24-14 AWG
2
0.2-2.5 mm
/ 24-14 AWG
7 mm / 0.27 inches
0.4 Nm
0.12-2.5 mm
2
/ 26-14 AWG
0.12-2.5 mm
2
/ 26-14 AWG
0.12-2.5 mm
2
/ 26-14 AWG
8 mm / 0.315 inches
0.4 Nm
-25...+70 °C
0...+60 °C (without derating)
-40...+85 °C
93 % at +40 °C, no condensation
4 kV; 1.2/50 s
2.5 kV; 1.2/50 s
500 V; 1.2/50 s
IEC/EN 61204
2006/95/EC
2004/108/EC
EN 50178, EN 60950, UL 60950, UL 508
SELV (EN 60950)
IEC/EN 61000-6-2
IEC/EN 61000-4-2, Level 4 (8 kV / 15 kV)
IEC/EN 61000-4-3, Level 3 (10 V/m)
IEC/EN 61000-4-4, Level 4 (4 kV)
IEC/EN 61000-4-5, Level 4 (2 kV sym.) Level 3 (3 kV asymmetrical)
IEC/EN 61000-4-6, Level 3 (10 V)
IEC/EN 61000-6-3
IEC/CISPR 22, EN 55022, Class B
IEC/CISPR 22, EN 55022, Class B
CP-S 24/20.0
horizontal
IP20 / IP20
I
2.5-10 mm
0.5-10 mm
0.5-16 mm
12 mm / 0.47 inches
1.2-1.5 Nm
2.5-10 mm
0.5-10 mm
0.5-16 mm
12 mm / 0.47 inches
1.2-1.5 Nm
3K3
2
2
/ 14-8 AWG
2
/ 20-8 AWG
2
/ 20-6 AWG
2
/ 14-8 AWG
2
/ 20-8 AWG
2
/ 20-6 AWG
16