Lutron PowPak RMK-ECO32-DV-B Guia De Instalacion página 2

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 3
PowPakR | Programming
R
Dimming Module with EcoSystem
041400
Part of the Energi TriPakR Family
Rev. A
12/2012
ALL PROGRAMMING IS OPTIONAL
Programming is not required for default functionality
Please consult individual component installation and programming guides
for more details.
Set a favourite light level
7
(Optional)
For Pico
Wireless Controls with a Preset Button
®
A
Adjust lights to desired level:
R
Use Raise " " or Lower " " on Pico
Wireless
Control.
B
Save favourite level:
Press and hold "Preset" for 6 seconds.
8
Set high-end trim for all fixtures
(Optional)
Setting High-End Trim:
Lighting electricity usage can be reduced
by 20% or more through high-end trim,
which sets the maximum light level for
each space.
For example, the human eye can barely
distinguish between a 100% and an 80%
light level—setting lights to 80% reduces
energy use by about 20%.
For best results, minimize the amount of sunlight entering the room
before performing the following procedure.
A
Enter trim adjustment mode:
Press & hold Raise "
" for 12 seconds.
Lights will flash high-low-high and top LED will be lit solid.
B
Adjust the high-end trim:
Use Raise "
" and Lower "
" to adjust and set the
lights to the desired high-end. (50 to 100%)
C
Save the high-end trim:
Press & hold All On "
" for 6 seconds to save setting.
Top LED will begin flashing and then turn off to indicate new level
has been saved.
9
Set minimum light level for all fixtures
(Optional)
Certain applications, such as hallways, may require that the lights
never turn off. For these areas, select the 10% option.
A
Enter minimum light level adjustment mode:
Press & hold Lower "
" for 12 seconds.
Lights will flash high-low-high and bottom LED will be lit solid.
B
Adjust the minimum light level:
Press Raise "
" to set low-end trim to 10%.
Press Lower "
" to set low-end trim to off.
C
Save the minimum light level:
Press & hold All On "
" for 6 seconds.
Bottom LED will turn off to indicate new level has been saved.
6
Device grouping
(Optional)
Device grouping allows
Windows
Pico
Wireless Controls and
®
Radio Powr SavrT Daylight
Sensors to control a group
Daylight
of lights instead of all lights
Sensor
Link
Test
in the room.
Default:
All Wireless
Transmitters
control all
light fixtures.
Enter Grouping
Start Grouping
A
B
Press and hold All On "
"
& Raise "
" for 6 seconds
R
until the Clear Connect
and
EcoSystemR LEDs begin
1
flashing at a rate of
second
2
1
ON
second OFF.
2
Link
Cal.
Test
First ballast/LED Driver will flash.
Note: Occupancy Sensors cannot be grouped and will
control all fixtures.
10
Set occupancy light levels
(Optional)
Note: Unoccupied light level is always the minimum light level and cannot be adjusted.
A
Set desired occupancy light levels:
Use Raise/Lower "
/
" buttons on the PowPakR Dimming Module or Raise/Lower "
Note: If certain lights should be unaffected by occupancy, turn lights off using Pico
B
Save occupancy light levels:
Press and hold " Test " for 6 seconds on any associated Radio Powr Savr
Release when Sensor lens starts to flash. Or, press and hold "Lights On" for 6 seconds on any associated Radio Powr Savr
Occupancy Sensor. Release when Sensor lens starts to flash.
11
Multiple-row daylighting
(Optional)
T
Radio Powr Savr
Daylight Sensor
Sensor must be grouped (Step 6)
Group sensor with ballasts before
beginning multiple-row daylighting.
Link
Cal.
Test
R
R
PowPak
Pico
Wireless
Control
Dimming Module
Lights On
Raise
All On
Raise
Preset
Lower
Lower
Lights Off
Need Help? www.lutron.com or call the Lutron Technical Support Center at +44.(0)20.7680.4481
Private office or small room
Grouping NOT required.
In small rooms such as private offices,
all lights should respond together and
grouping is not required.
R
PowPak
Dimming
For more information:
Module
www.lutron.com/powpakdimming
Pico
®
Wireless
Control
Assign Fixtures
C
Assign / Unassign
Hold Lights
Tap
Off "
"
Lights On
"
6 Seconds
Hold "Link"
Tap "Cal."
6 Seconds
Link
k
Cal.
Test
Test
Assigned: Bright
Unassigned: Dim
/
" on an associated PicoR Wireless Control(s)
R
Wireless Control(s).
T
Occupancy Sensor without a "Lights On" button.
Press and hold All On "
" and Lower "
" on the PowPakR Dimming Module for
A
6 seconds. Fixtures not controlled by the Daylight Sensor will go to OFF, all others will go to
low end. (First ballast will begin to flash.)
B
Press Raise "
" on PowPakR Dimming Module, or Lights On "
R
Pico
Wireless Control to toggle the fixture from Window Row (low-end) to Inside Row
(high-end), or vice versa.
C
Press Lower "
" on PowPakR Dimming Module, or Lights Off "
R
Pico
Wireless Control to move to the next fixture. (Next fixture will flash.)
D
Repeat steps B and C until all rows have been properly set up.
Press and hold All On "
" on PowPakR Dimming Module, or "Preset" on any associated
E
PicoR Wireless Control for 6 seconds. (Window Row will begin to flash.)
F
Using the Raise/Lower "
/
" buttons on the PowPakR Dimming Module or Raise/Lower
"
/
" on an associated PicoR Wireless Control set the current row to your desired light
level.
G
Tap All On "
" on the PowPakR Dimming Module or Lights Off "
R
associated Pico
to move to the next row.
Wireless Control
H
Repeat steps F and G until both rows are properly set up.
Press and hold " Cal. " on the daylight sensor to calibrate room. See step 5 of
I
"Daylight calibration" on reverse.
Windows
Radio Powr
WINDOW ROW
Occupancy
R
PowPak
Link
Test
Dimming
Daylight
Module
Sensor
INSIDE ROW
Pico
®
Wireless
Controls
Repeat until all fixtures have been
Save Grouping
D
assigned / unassigned
Next Fixture
Tap
Lights Off
"
"
"
Tap "Link"
Link
Link
Test
Test
This will save current group.
Selected ballast/LED Driver
Repeat B-D for other Wireless
will flash.
Transmitters.
Limited Warranty
Lutron EA Ltd. ("Lutron EA") warrants each unit to be free from defects in
.
material and workmanship and to perform under normal use and service. To the
extent permitted by law, Lutron EA and Lutron Electronics Co. Inc. ("Lutron")
make no warranties or representations as to the units except as set forth herein.
This warranty shall run for a period of two years from the date of purchase and
Lutron's obligations under this warranty are limited to remedying any defect,
T
replacing any defective part or replacement (at Lutron EA's sole option) and shall
be effective only if the defective unit is shipped to Lutron EA postage prepaid
within 24 months after purchase of the unit. Repair or replacement of the unit
does not affect the expiry date of the warranty. This warranty does not cover
damage or deficiencies due to abuse, misuse, inadequate wiring or insulation or
use or installation other than in accordance with instructions accompanying the
unit.
To the extent permitted by law, neither Lutron EA nor Lutron shall be liable for
any other loss or damage including consequential or special loss or damages,
" of any associated
loss of profits, loss of income, or loss of contracts arising out of or relating to the
supply of the unit or the use of the unit and the purchaser assumes and will hold
harmless Lutron EA and Lutron in respect of all such loss or damage. Nothing in
this warranty shall have the effect of limiting or excluding Lutron EA's or Lutron's
" on any associated
liability for fraud or for death or personal injury resulting from its own negligence,
or any other liability, if and to the extent that the same may not be limited or
excluded as a matter of law.
This warranty does not affect the statutory rights of consumer
purchasers of this product.
Although every attempt is made to ensure that catalogue information is accurate
and up-to-date, please check with Lutron EA before specifying or purchasing
this equipment to confirm availability, exact specifications, and suitability for your
application.
Lutron, Pico, PowPak, Energi TriPak, Clear Connect, EcoSystem and
" on any
registered trademarks and Radio Powr Savr is a trademark of Lutron
Electronics Co., Inc.
©2012 Lutron Electronics Co., Inc.
Large office or classroom
Grouping RECOMMENDED.
T
Savr
In large rooms such as conference rooms
Sensor
or classrooms, separate control of some
fixtures, such as whiteboard lights or
daylighting rows, is beneficial. Grouping
is recommended.
For more information:
www.lutron.com/powpakdimming
Exit Grouping
E
Press and hold All On
"
" & Raise "
" for
Hold Lights
6 seconds until LEDs
stop flashing.
Off "
"
6 Seconds
Hold "Link"
6 Seconds
are
Lutron EA Ltd | 6 Sovereign Close
London, E1W3JF, UK
loading