Dip Switch Setting - LG Multi V Water IV ARWN080LAS4 Manual De Instalación

Ocultar thumbs Ver también para Multi V Water IV ARWN080LAS4:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

26
Automatic Addressing
The address of indoor units would be set by Automatic Addressing
- Wait for 3 minutes after supplying power.
(Master and Slave outside unit s, indoor units)
- Press RED button of the outside unit s for 5 seconds. (SW01C)
- A "88" is indicated on 7-segment LED of the outside unit PCB.
- For completing addressing, 2~7 minutes are required depending on
numbers of connected indoor units
- Numbers of connected indoor units whose addressing is completed are
indicated for 20 seconds on 7-segment LED of the outside unit PCB
- After completing addressing, address of each indoor unit is indicated
on the wired remote control display window. (CH01, CH02,
CH03, ......, CH06 : Indicated as numbers of connected indoor units)
[MAIN PCB]
DIP-SWITCH 7 - Segment
SW04C ( : cancel)
SW03C ( : forward)
SW02C ( : backward)
SW01C (
: confirm)
SW01D (reset)
CAUTION
!
• In replacement of the indoor unit PCB, always perform Automatic
addressing setting again (At that time, please check about using
Independent power module to any indoor unit.)
• If power supply is not applied to the indoor unit, operation error
occur.
• Automatic Addressing is only possible on the master Unit.
• Automatic Addressing has to be performed after 3 minutes to im-
prove communication.
The Procedure of Automatic Addressing
Power On
Waiting 3 minutes
Press RED Button for 5 sec.
(SW01C)
Automatic addressing start
7-segment LED
= 88
Don't press RED Button
(SW01C)
• Automatic addressing setting end
Numbers of indoor unit connection set whose
addressing is completed are indicated for 30seconds
Waiting about 2~7 minutes
on 7-segment LED after completing setting
NO
7-segment LED
= 88
YES
Indoor address number is displayed on wired remote control or
indoor unit display window. It is not an error message, will
disappeared when on/off button is pressed on remote control
ex) Display of 01, 02, ..., 15 means connection of 15 indoor units
OK
and Automatic addressing is completed normally.

Dip switch setting

Setting the function
Select the mode/function/option/value using '▶', '◀' Button and con-
firm that using the ' ' button after dip switch No.5 is turned on.
!
CAUTION
It is only executed when all indoor units are off.
Mode
Content Display1
In-
stal-
lation
* Functions save in EEPROM will be kept continuously, though the
system power was reset.
To cancel the function you need to set OFF.
Group Number setting
Group Number setting for Indoor Units
- Confirm the power of whole system(Indoor Unit, Outside Unit) is
OFF, otherwise turn off.
- The communication cables connected to CEN.A and CEN.B terminal
should be connected to central control of Outside Unit with care for
their polarity (A-A, B-B ).
- Turn the whole system on.
- Set the group and Indoor Unit number with a wired remote control.
- To control several sets of Indoor Units into a group, set the group ID
from 0 to F for this purpose.
Outside Units (External PCB)
SODU.B SODU.A
B
Check the connections
Example) Group number setting
of communication cable
st
1
number indicate the group number
2nd number point out indoor unit number
DIP-SW01 7 - Segment
SW04C ( : cancel)
SW03C ( : forward)
SW02C ( : backward)
SW01C (
SW01D (reset)
Function
Option
Content
Display2
Content
Display3 Content Display4 Implement Display5
Cool & Heat
oFF op1~
Selected
Selector
op2
the option
Geothermal
Selected
mode set-
on
oFF
the option
ting
Sol. Valve
Selected
200 V out-
on
oFF
the option
put
Variable
Selected
water flow
on
oFF
the option
control
Outside unit
-
-
address
Target
oFF op1~
Selected
pressure
op4
the option
adjusting
Use Sump
Selected
on
oFF
Heater
the option
IDU capacity
Selected
adjusting
the option
on
oFF
IDU.B
IDU.A
CEN.B
CEN.A
A
B(D)
A(C)
1 F
Group Indoor unit
: confirm)
Value
Action
Remarks
Change
Save in
-
-
the set
Blank
EEPROM
value
Change
Save in
-
-
the set
Blank
EEPROM
value
Change
Save in
-
-
the set
Blank
EEPROM
value
Change
Save in
-
-
the set
Blank
EEPROM
value
set
Change
Save in
0~254
the
the set
Blank
EEPROM
value
value
Change
Save in
-
-
the set
Blank
EEPROM
value
Change
Save in
-
-
the set
Blank
EEPROM
value
Change
Save in
-
-
the set
Blank
EEPROM
value
DRY1
DRY2
GND
12V
Tabla de contenido
loading

Este manual también es adecuado para:

Multi v water iv arwn100las4Multi v water iv arwn120las4Multi v water iv brwn080las4Multi v water iv brwn100las4Multi v water iv brwn120las4Multi v water iv arwn140las4 ... Mostrar todo

Tabla de contenido