Motor overload protection
MOVIMOT
thermal memory retention upon shutdown or power loss.
The trip current is adjusted to 140 % of the rated motor current.
Ambient temperature
MOVIMOT
derated output current. To determine the output current rating at higher than 40 °C,
the output current should be derated 3.0 % per °C between 40 °C and 60 °C.
•
•
®
MM..D is provided with load and speed-sensitive overload protection and
®
MM..D is suitable for an ambient temperature of 40 °C, max. 60 °C with
Only use certified units with a limited output voltage (V
output current (I ≤ 8 A) as an external DC 24 V voltage source.
The UL certification only applies for the operation on voltage supply systems with
voltages to ground of max. 300 V. The UL-certification does not apply to operation
on voltage supply systems with a non-grounded star point (IT systems).