2.2 RX Receiver Wiring (RF models only)

RX1
ELECTRONICS
GB
GB
N L
FR
ES
1) For mains voltage operated systems link terminal 2 to mains live supply.
2) Power supply to unit must not be switched by timeswitch.
NL

3.0 Commissioning (RF models only)

GR
I M P O R T A N T
On initial installation, or if the batteries have been removed
PL
from the unit for more than 1 minute before beginning
programming or commissioning the TP4000 unit; it is essential
CZ
that the RESET button be pressed to ensure the factory preset
programmes are set and the system is fully operational.
TR
If the thermostat and the receiver have been supplied together
in a combined pack, the units have been paired in the factory
HR
and no commissioning is required (RX1 only).
To make the RX receiver learn the thermostat's signal, follow steps 1-5
RO
below.
HU
Step 1
TP4000-RF - Reset the unit by pressing the recessed reset button.
LT
Step 2
Press and hold V and + buttons for 3 seconds
(TP4000 RF now transmits unique signal
continuously for 3 minutes).
6
1 2 3 4
COM
ZONE
ZONE
1 ON
1 OFF
RX2 & RX3
ELECTRONICS
A
B C 1 2 3 4 5 6
L
N
COM
TERMINAL 6
RX3 ONLY
ZONE
ZONE
ZONE
ZONE
1 ON
1 OFF
2 ON
3 ON
TP4000