Technical Specifications - Nice HSSOC Instrucciones Y Advertencias Para La Instalación Y El Uso

Ocultar thumbs Ver también para HSSOC:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 5
ENGLISH
1 - SPECIAL WARNINGS
Install the product in a location difficult to reach, to avoid intentional damage, pos-
sibly in a location where the sound produced can be propagated efficiently in the
required directions. If necessary, fit additional sirens.
2 - PRODUCT DESCRIPTION AND INTENDED USE
HSSOC is an outdoor wired siren with a sound power of 105 dB; designed to signal
intrusion and also to dissuade intruders.
Powered by the control panel, it envisages a backup battery (12 V 2.2 Ah) also for
operation in the event of a power failure; suitable for outdoor use.
Any other use is to be considered improper and is strictly prohibited! Nice declines
all liability for damage resulting from improper use of the product and other than as
specified in this manual.
3 - OPERATION
HSSOC signals intrusion with a powerful acoustic alarm. On each alarm trip from the
control panel (+N), it emits an alarm signal lasting approx. 3 minutes; the alarm signal
terminates when the control panel is deactivated.
If the "alarm block" connection is envisaged (T/C connected to +OFF of control
panel) when the control panel is off, the siren is "blocked"; i.e. even if the alarm
is activated (+N), no acoustic signal is activated, which normally occurs when the
control panel is ON.
Also, for each control panel arming phase, the acoustic signals occur each time the
alarm (+N) is armed, only until the programmed count is reached; the siren is then
blocked when this number is exceeded.
The cycle count is reset when the control panel is switched off.
Luminous signals:
• 4 flashes = confirms arming of the control panel
• 1 flash = confirms disarming of the control panel
4 - PROGRAMMING
HSSOC does not require special programming. However, 2 settings are required
before marking the electrical connections:
a) T/C block command: positive (+) or negative (-); for HSCU1C and HSCU1GC
units, leave set to +.
b) Alarm signal block: after 3 or 5 alarm cycles.
CAUTION! - The "EXT ALARM" function MUST NOT BE ENABLED.
+
-
+
BATT ALIM
5 - INSTALLATION
CAUTION! – All electrical connections must be made with the unit discon-
nected from the mains power supply.
01. Open the box (fig. 1);
02. Prepare the hole for the routing of cables: detach the plastic part as shown in fig.
2. Caution! – Do not dispose of the plastic element removed; it is used subse-
quently to activate the tamper-proof system if required (point 03);
03. Before mounting HSSOC on the wall, if required, the tamper-proof system can
be activated; this means that if the box is opened, detached from the wall and/
or broken into, the siren transmits the event to the control unit for activation of an
acoustic and visual signal. To activate this function, proceed as shown in fig. 3.
04. Route the electric cables through the hole and fix HSSOC to the wall by means
of the screws and plugs supplied (fig. 4);
05. Before making the electrical cable connections, the required operating mode
must be selected (fig. 5):
a) with alarm block: with the alarm active, when the set number of alarms is
exceeded, the alarm signal is shut off;
b) without alarm block: with the alarm active, the alarm signal is continuous;
06. Make the electrical connections on HSSOC:
- buffer battery (not supplied): see fig. 6, the lamp flashes (if the lamp is per-
manently lit, this means that the battery is not inserted correctly);
- power supply from control unit: see fig. 7;
To connect the control unit power supply, refer to the relative instruction manual.
HSSOC confirms correct connection by emitting 2 beeps and the lamp stops
flashing;
07. Close the box (fig. 8); HSSOC emits a beep to confirm correct closure; if this
does not occur, check closure.
HSSOC performs a self-programming function when activated/deactivated for the
first time on the control unit (see control unit instruction manual).
6 - ELECTRICAL CONNECTION TO CONTROL UNIT
To make the electrical connection to the control panel, refer also to chapter 5 in this
-
+N
TAMP
T/C
+
-
instruction manual.
BATT +/-: electrical connection to backup battery. The Pb-12V. 2.2Ah backup bat-
tery (not supplied) is indispensable for siren operation.
ALIM +/-: electrical power supply connection from control panel ( P.SUPPLY - =
GND; P.SUPPLY + = +SAA)
+ N: positive "on absence" which activates the alarm (if block is not present on T/C).
TAMPER: output (voltage-free contact) for tampering alarm, for tamper alarm input
connection on control panel (between GND and TMP A or B or C). Otherwise the
tamper contact can be connected in series to + N.
T/C: block command, for connection to control panel armed/disarmed signal
(+OFF).
For electrical connections, proceed in the following sequence:
01. the lamp starts flashing (it remains lit if the battery connection is inverted);
02. connect the power supply to the control panel: P.SUPPLY + and - ;
03. connect the +N activation signal: the lamp stops flashing immediately and 2
acoustic signals are emitted for approx. 2 seconds to confirm the siren standby
status;
04. connect the tamper output;
05. if present, connect the T/C alarm block command.
7 - BUFFER BATTERY REPLACEMENT
01. Set the control unit to "TEST" mode (see control unit instruction manual);
02. Open the HSSOC box (fig. 1);
03. Disconnect the buffer battery, replace with a new battery of the same type and
then reconnect, observing the specified polarity (fig. 5): the control unit emits a
beep to confirm successful learning;
04. Close the box (fig. 9); HSSOC emits a beep to confirm correct closure; if this
does not occur, check closure.

8 - TECHNICAL SPECIFICATIONS

WARNINGS: • All technical specifications stated in this section refer to an ambient
temperature of 20°C (± 5°C). • Nice S.p.a. reserves the right to apply modifications
to products at any time when deemed necessary, maintaining the same intended
use and functionality.
n Type: outdoor siren with cable connection to control unit and built-in flashing light
n Power supply: 12 Vdc + 2.2 Ah buffer battery with estimated autonomy of 4
b
days
n Acoustic alarm: 105 dB(A) at 1 m Frequency 1400 - 1600 Hz
n Visual alarm: lamp 5 W, 12 V flashing
a
n Autonomy: 4 days with buffer battery
n Absorbed current: on standby maximum 5 mA - 2 A in alarm status
n Protections: internal battery anti-inversion device
n Timers: max. 3 minutes for each flashing light – count control of 3 or 5 alarms
n Radio reception/transmission: digital bidirectional communication, in dual
band frequency (433 and 868 MHz) with quartz control; devices pre-encoded in
the factory and managed in self-learning mode
n Radio range: 100 m in open field free of disturbance or approx. 20 m inside
buildings.
n Insulation: class II
n Operating temperature: from -20 °C to +55 °C
n Use in class III environments
n Assembly: vertical, wall-mounted.
n Dimensions (mm): 207 x 203 x 73 mm
n Weight: 1.560 kg
+OFF
GND
+SAA
+N
BATTERY
+
-
+
-
BATT
ALIM
+N
TMPA
TAMPER
T/C
Tabla de contenido
loading

Tabla de contenido