MPPES
5
Commissioning
1. Supply the MPPES-... with direct current
(supply voltage U
= DC 24 V).
v
2. Pressurise the MPPES-... with an input pressure higher than the
maximum desired output pressure.
3. Supply current to the MPPES-... with a setpoint value signal
corresponding to the valve type (current/voltage variant).
A proportional output pressure P
To the setpoint value signal range DC 0 ... 10 V or 4 ... 20
mA are assigned the following pressure ranges, depending
on the design (
Type
MPPES-...-(P
)-P
-010
u
o
)-P
MPPES-...-(P
-420
u
o
e.g. standard design
MPPES-1/4-2-010
e.g. special adaptation
MPPES-1/2-1,5-7-420
Tab. 15
For visual inspection of the control process at the MPPES-...:
• Wire the MPPES-... with the following measuring device according
to Fig. 13/Fig. 14:
• Use for the
– voltage variant a voltage measuring device
and for the
– current variant a current measuring device (ammeter).
The actual electrical value can be tracked on the display of the meas-
uring device. This changes proportional to the pressure curve at port
2.
20
is then adjusted to.
s
Tab. 15):
Setpoint signal range
DC 0 ... 10 V
4 ... 20 mA
DC 0 ... 10 V
4 ... 20 mA
Fig. 11
Fig. 12
Pressure range
P
... P
bar
u
o
0 ... 2 bar (
Fig. 14)
1.5 ... 7 bar (
Fig. 14)
Fig. 13
Voltage
measuring device
Fig. 14
Ammeter
Festo – MPPES – 1304d English