Flat roof
30° roof
45° roof
2.5.1 
Sizing of flue
The.correct.sizing.of.the.flue.is.an.essen-
tial. condition. for. efficient. boiler. opera-
tion..
The.main.factors.to.be.taken.into.consi-
deration. for. calculating. the. section. are.
the. heat. input. of. the. boiler,. the. type. of.
fuel,. the. percentage. of. CO 2 ,. the. mass.
flow.of.smoke.at.nominal.load,.the.tem-
perature.of.the.smoke,.the.roughness.of.
the.internal.wall,.and.the.effect.of.gravity.
on. the. draught. pressure,. which. must.
take.into.account.the.external.tempera-
Tetto piano
> 5 m
Tetto a 30°
> 1,30 m
≤ 1,30 m
Tetto a 45°
> 1,50 m
≤ 1,50 m
ture.and.the.altitude..
2.6 
ELECTRICAL 
CONNECTION
The. boiler. is. supplied. with. an. electric.
cable.. Should. this. require. replacement,.
it. must. be. purchased. exclusively. from.
SIME..
The. electric. power. supply. to. the. boiler.
must. be. 230V-50Hz. single-phase. throu-
gh. a. fused. main. switch,. with. at. least. 3.
mm.spacing.between.contacts..
≤ 5 m
Volume
tecnico
Colmo
Zona di reflusso
30 °
Colmo
Zona di reflusso
45 °
The. room. stat. must. be. class. II. as. spe-
cified. by. standard. EN. 60730.1. (clean.
contact).
NOTE:  Device  must  be  connected  to  an 
efficient earthing system. 
SIME  declines  all  responsibility  for 
injury  or  damage  to  persons,  animals 
or  things,  resulting  from  the  failure 
to  provide  for  proper  earthing  of  the 
appliance. 
Always turn off the power supply before 
doing any work on the electrical panel.