Commissioning

Before switching on

(
Stop!
Before switching on the standard device with the communication module for
the first time, check the entire wiring for completeness, short circuit and earth
fault.

Setting the node address

ƒ In case of several interconnected Ethernet POWERLINK nodes, the addresses must
differ from each other.
ƒ For each device, the node address at the DIP switches 1 ... 128 and in code C13044 /
C14044must be set identically.
ƒ Valid node address in the Ethernet POWERLINK network:
Node address
240
1 … 100
1 … 239
ƒ Lenze setting of the DIP switches 1 ... 128 = OFF (invalid value "0")
ƒ The housing labelling corresponds to the valencies of the individual DIP switches for
determining the station address.
EDK94AYCEP DE/EN/FR/ES/IT 4.0
Meaning
E94AYCEP is a managing node.
E94AYCEP is a controlled node with another E94AYCEP as managing node.
E94AYCEP is a controlled node with a managing node of a different
manufacturer.