6 INITIAL SETUP FOR A NEW SYSTEM – MINIMUM SETUP
Upon installation of a new system, several items need to be configured before the system will operate properly . The
items that must be configured for proper operation are:
• Assignment of controller to valve
• Valve Calibration
Other options, such as units of measure, valve name, display brightness etc ., can be configured at any time via the
Setup Menu, but are not required for proper system operation during initial installation .
Assigning a Valve
Before controlling a valve or displaying sensor readings, the Style 9323 Navigator Pro must be assigned to a valve . This
step tells the display what valve it is controlling . In order for the assignment to take place, the desired valve must be
powered and connected to the Navigator Pro via a CAN network (see the "GENERAL INSTALLATION" section above for
wiring instructions) . Valve assignment will only need to be performed once and can be changed at a later time via the
Setup Menu if required .
There are two ways to assign a valve: automatically or manually . If there is only one valve installed on the CAN network
(e .g . one or more display(s) are connected directly to one valve), all displays on the network will automatically be as-
signed to that valve . If there is more than one valve on the network, the appropriate valve will need to be selected manu-
ally . There are two opportunities to select the valve manually:
• At first power up .
• At any time from the Setup Menu (see the "VALVE ASSIGNMENT" section below) .
When the assignment process begins (either at startup or through the Setup Menu), the Navigator Pro will display a list
of serial numbers of all powered valves connected via the CAN network . The serial numbers in the list correspond to the
labels affixed to each valve as shown below .
Valve Serial number location (need updated picture)
Use the
RED and
GREEN buttons to scroll through the list until the desired valve serial number is highlighted . Then
press the ■ SET button to assign the selected valve .
Note: The Navigator Pro cannot be assigned to more than one valve. The Navigator Pro will remember its as-
signed valve even when the power is off.
Once the Navigator Pro has been successfully assigned to a valve, the screen will proceed to the main operational
screen . The Navigator Pro can now be used to open and close the valve . However, valve calibration must be performed
in order to display valve position properly .
Valve Serial
Number location
2-23/32"
Page 08
9-7/8"