Installation
Wiring
1
L
1
3
G
Wiring
Connect the power wires to the switch terminals and connect
the ground wire to the ground terminal block inside the
enclosure. Reference the National Electric Code and all local
codes for appropriate wire size and grounding requirements.
See chapter Cabling. All cables must have 167 °F / 75 °C
minimum rating.
Switch terminals are not intended to support the weight of the
cables, so installer must provide adequate cable support. To
avoid placing a strain on the line and load terminals, bend the
cable carefully. Undue strain may cause terminal distortion and
adversely affect the performance of the switch.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
See general safety instructions on page 1/2 before proceeding.
Failure to follow these instructions will result in death or serious injury.
1/12 Installation | Instruction Bulletin EOHU364K, EOHU365K, EOHU366K, 1SCC340037M1401 / A
Safety
switch
Line and load side
size [A]
terminal lugs
Wire range [kcmil/mm
2
]
200
2 - 600 / 35 - 300
400
(2) #2 - 600 / 2 × 35 - 300
600
(2) #2 - 600 / 2 × 35 - 300
Wire strip length L [in / mm]
200
1.10 - 1.18 / 28 - 30
400
1.34 - 1.42 / 34 - 36
600
1.34 - 1.42 / 34 - 36
Wire tightening torque
[lbs.in]
[Nm]
200
375
41.8
400
500
55.7
600
500
55.7
2
Ground bus
#14 - 2 / 2.5 - 35
#6 - 250 / 10 - 120
#6 - 250 / 10 - 120
0.39 - 0.47 / 10 - 11.9
0.91 - 0.99 / 23 - 25
0.91 - 0.99 / 23 - 25
[lbs.in]
[Nm]
50
5.6
275
31.1
275
31.1