2.7.4 Connection and choice of cables
For all connections, use flexible, strong rubber-sheathed cables which comply with standard IEC 60245-4 or equivalent cables, and
ensure that these are kept in perfect condition. Only use one class I electrical device per socket and connect up equipment using a
cable equipped with a PE protective conductor (green/yellow); this protective conductor is not required for class II equipment.
Adhere to the cross sections and lengths recommended in this table during installation or when using electrical extensions.
Generating set type:
Generating set socket type:
Recommended cable cross section:
Length of
cable used
101 to 150 m*
*This cable length is the maximum permitted length, and must not be exceeded.
Installation method = cables on raceway or non-drilled tablet/Permitted drop in voltage = 5%/Multi-core conductors/Cable type PVC
70°C (e.g. H07RNF)/Ambient temperature =30°C.
2.8
Risks during handling operations, use and maintenance
For safety reasons, all operations must be carried out by staff with the necessary skills and using suitable equipment. Maintenance
must be carried out regularly and properly using only original or equivalent parts. Gloves must be worn.
Safety guidelines for handling petroleum products:
DANGER
Safety guidelines for handling batteries:
DANGER
3 Getting started with the generating set
3.1
Key to illustrations
The cover illustrations can be used to identify the various components of the generating set. The procedures in the manual refer to
these illustrations using letters and numbers as identifiers, for example, (A1) refers to the number 1 on figure A.
Oil dipstick/filler plug
Filler neck
Fuel level indicator
Fuel tank cap
Screen filter
Fuel tap
Choke
Switch
Starter-recoil reel handle
Operating light
10 A
mm²
0 to 50 m
4
51 to 100 m
10
10
RISK OF EXPLOSION
Respect the local regulations in force concerning the handling of petroleum products.
Filling should be carried out with the engine switched off and cold. Smoking, using a
naked flame or producing sparks are forbidden while the fuel tank is being filled. After
filling, always check that the tank's filler cap is properly tightened. Clean any traces of
fuel with a clean cloth and wait until the vapours have dispersed before starting the
generating set.
The fluids used by generating sets, such as oils and fuels, are dangerous products.
Never ingest them. Avoid prolonged or repeated contact with the skin.
RISK OF POISONING OR EXPLOSION
Follow the battery manufacturer's recommendations. Use insulated tools
only. Never use sulphuric acid or acid water to top up the electrolyte level.
Never leave the battery close to a flame or fire. Always ensure adequate
ventilation during charging.
A1-B2
Electrical sockets
B3
Oil drain screw
A2
Fuel filter
A3
Fuel filter mounting clips
A4
Side panels
A5
Sediment bowl
A6
Sediment bowl cover
A7
Seal
A8
Air filter
A9
Air filter cover
Single phase
16 A
AWG
mm²
AWG
mm²
10
6
9
7
10
7
7
16
5
A10
A11-B1
A12
A13
A14
A15-C3
C1
C2
A16
D2
Three-phase
32 A
10 A
AWG
mm²
AWG
10
7
1.5
14
25
3
2.5
12
35
2
4
10
Foam element
Spark arrester
Spark arrester mounting
bolt
Exhaust silencer
protection
Fuel drain screw
Spark plug
Spark plug cap
Circuit breakers
Earth connection
16 A
mm²
AWG
2.5
12
4
10
6
9
D3
A17-E2
E1
E3
C5
A18-F2
F1
A19
A20