3. Installation Guidelines
Failure to comply with all aspects of these instructions may result in unsafe perfor-
mance.
All installations must comply with relevant State, Provincial and Local Authority re-
quirements.
Delivery Temperature:
Every valve is factory set for 120°F (49°C) outlet temperature, with a 140°F (60°C )hot
water inlet temperature.*
To Achieve Maximum Hot Water Delivery Performance
To achieve maximum hot water delivery performance, the TANK BOOSTER must first
be installed on the water heater in accordance with these instructions. Once in-
stalled consult the water heater manufacturer's instructions and increase the tem-
perature control device to around 140°F (60°C). This has the added benefit of being a
temperature determined by the OHSA as being sufficient to kill Legionella bacteria.
Verify the outlet temperature of the TANK BOOSTER and adjust in accordance with
these instructions.
Non Return (Check) Valves:
Non return valves are integrated in the cold and hot water inlets of the valve. For
correct and safe system function, ensure that the check valve is clean of debris and
functioning correctly.
*NOTE: To ensure delivery of the desired mixed water temperature at the outlet the installer must
adjust and verify the temperature at the outlet by carefully following instructions on the following
page.
TANK BOOSTER
Installation Instructions