Cash Acme TANK BOOSTER HEATGUARD 020 Serie Manual Del Usuario página 22

Ocultar thumbs Ver también para TANK BOOSTER HEATGUARD 020 Serie:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

FAULT / SYMPTOM
No flow from the valve out-
let.
Flow rate reduced or fluctu-
ating.
Mixed water temperature
does not change when tem-
perature adjuster is altered.
Hot water flows into the
cold water system or vice
versa.
Valve is noisy.
TANK BOOSTER
Installation Instructions
IS279 REV L
2-17-16
CAUSE
Hot or cold water supply
failure.
Strainers are blocked.
Strainers are blocked.
Fluctuating supply pres-
sures.
Hot and cold supplies are
reversed.
Non-return valves fouled.
Excessive water velocity.
Valve sized incorrectly.
22
RECTIFICATION
Restore inlet supplies and
check mix temperature.
Clean strainers.
Clean Strainers.
Install pressure regulating
valves.
Refit the valve with Hot/
Cold supplies fitted to the
correct connections.
Clean non-returns ensuring
debris is removed.
Reduce water velocity (best
achieved by fitting a pres-
sure regulating valve).
Check valve specifications
and ensure the appropriate
valve is used for required
flow.