Unit Installation

15.0
538.0
32.0
529.0
580.0 ~ 610.0mm (Ceiling Board Opening)
Unit Hanging
Indoor Unit
Drain Piping Work
Flexible Hose
Pipe Clamp
Indoor
Unit
Panel
Drain Test
Feed Water
Flexible Drain Hose
NOTE
This indoor unit uses a drain pump for condensed water drainage. Install the unit horizontally to prevent water leakage
or condensation around the air outlet.
18.0
19.0
Ceiling
Board
35.0mm
Ceiling
Main Drain Pipe
Measure and mark the position for the hanging rod.
Drill the hole for the angle nut on the ceiling and fix
the hanging rod.
The installation template is extended according to
temperature and humidity. Check on dimensions in
use.
The dimensions of the installation template are the
same as those of the ceiling opening dimensions.
Before ceiling laminating work is completed, be
sure to fit the installation template to the indoor unit.
NOTE
Be sure to discuss the ceiling drilling work with the
installers concerned.
Confirm the pitch of the hanging rod.
Hold the unit and hang it on the hanging rod with
the nut and washer.
Adjust the unit height to 35.0mm between the
indoor unit bottom surface and the ceiling surface.
Confirm with a level gauge that the unit is installed
horizontally and tighten the nut and bolt to prevent
unit failing and vibration.
Open the ceiling board along the outer edge of the
paper installation template.
Drain pipe must be in downward gradient for
smooth drainage.
Avoid installing the drain pipe in up and down slope
to prevent reversed water flow.
During the drain pipe connection, be careful not to
exert extra force on the drain connector at indoor
unit.
The outside diameter of the drain connection at the
flexible drain hose is 20mm.
Be sure to execute heat insulation (polyethylene
foam with thickness more than 8.0mm) on the drain
piping to avoid the condensed water dripping inside
the room.
Connect the main drain pipe to the flexible drain.
Feed water from flexible drain hose to check the
piping for leakage.
When the test is completed, connect the flexible
drain hose to the drain connector on the indoor unit.
1-4