Important Notice; Installation Of The Indoor Unit - Daikin FWF02CATNMV1 Manual De Instalación

Unidades de serpentín de ventilador de agua fría
Ocultar thumbs Ver también para FWF02CATNMV1:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 44
Preliminary Site Survey
Obstacle
Voltage supply fluctuation must not exceed ±10% of rated voltage. Electricity supply lines must be independent of
welding transformers which can cause high supply fluctuation.
Ensure that the location is convenient for wiring, piping and drainage.
The indoor unit must be installed in such that is free from any obstacles in path of cool air discharge and warm air
return, and must allow spreading of air throughout the room (near the center of the room).
Provide clearance for the indoor unit from the wall and obstacles as shown in the figure.
The installation place must be strong enough to support a load 4 times the indoor unit weight to avoid amplifying noise
and vibration.
The installation place (hanging ceiling surface) must levelled and the height in the ceiling is 350mm or more.
The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).

IMPORTANT NOTICE

CORK TAPE FULLY INSULATED
INSULATION THROUGH OUT CHILLED WATER PIPING

INSTALLATION OF THE INDOOR UNIT

Min. 0.5m
Min. 0.5m
Floor
1-3
Min. 0.5m
Tabla de contenido
loading

Este manual también es adecuado para:

Fwf03catnmv1Fwf04catnmv1

Tabla de contenido