Commissioning
2.1.

Teach-in

2.1.1.
Assignment to underfloor heating
controller
In order to assign a temperature zone to the HCW 82/
HCF 82, follow the instructions from the chapter entitled
"Start-up" in the "Underfloor heating controller
HCE 80/HCE 80R/ HCC 80/HCC 80R" installation
instructions.
2.1.2.
Assignment to Hometronic Manager
HCM 200D
In order to assign a temperature zone to the HCW 82/
HCF 82, follow the instructions from the chapter entitled
"Installing the HCW 82/HCF 82 and assigning it to a room"
in the Hometronic Manager HCM 200D operating
instructions.
2.1.3.
Assigning an HCF 82 for frost
protection function
The HCW 82/HCF 82 can only be assigned to
the Hometronic Manager as a frost protection
sensor if the device switch HS 30 is used for the
boiler request.
Proceed as follows in order to assign the HCF 82 as a frost
protection sensor:
Press the Input button.
The Hometronic Manager is
in the "Settings" menu.
Go to the "Installation" menu.
Go to the "Boiler request" menu.
Turn the Input button until
"Frost protec. sensor" is
selected.
Press the input button.
The cursor flashes next to the "Frost protec. sensor". The
Hometronic Manager is ready to receive data from the
sensor.
Activate the teach-in function within 4 minutes by pressing
the Send button at the room temperature sensor
(see Fig. 2, Send button).
After successful teach-in, a * appears next to "Frost
protec. sensor" in the display of the Hometronic Manager:
The room temperature sensor is assigned to the
Hometronic Manager for the frost protection function.
For information on how to read measured data of
the room temperature sensor at the Hometronic
Manager or adapt the threshold value for the
frost protection function, please refer to the
operating instructions of the Hometronic
Manager.
8
DE-INSTALLATION
DE-INSTALLATION

INSTALLATION

DAYLIGHT SAVING
DE-INSTALLATION
DAYLIGHT SAVING
TIME
DAYLIGHT SAVING TIME
TIME
SENSOR FUNCTION
SENSOR FUNCTION
SWITCHING MODULE
FROST PROTEC.
SENSOR
2.1.4.

Failed teach-in

If the teach-in has failed:
Improve the data transfer (see below).
Repeat the teach-in.
Improving the data transfer
When selecting the operating site of each device ensure
that the distance to radio devices such as radio
headphones, cordless phones, etc. according to the DECT
standard amounts to at least 1 m.
Do not install the devices over metallic wall connecting
sockets and at least 30 cm away from the cover of the heat
generator.
Correct the installation site of the room temperature sensor
if necessary.
2.2.
Installation
Remove the batteries.
Mark the drill holes according to the drilling template
(see Fig. 3).
Fig. 3: Drilling scheme (measurements in mm)
Drill the holes.
Screw on the room temperature
sensor.
Re-insert the batteries.
Place the housing cover in
position above and snap it down
(see Fig. 4).
Fig. 4:
Placing housing cover in
position