Functions And Options - Resol FriWa Montaje/Conexiones/Manejo

Ocultar thumbs Ver también para FriWa:
Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

FriWa
Description
Preset temperature hotwater
Block protection accelaration time
Block protection end time
Block protection tap wait time
Status function blocking protection
Time blocking protection
Minimum rotational speed
Pump start impulse
Tap identification
Maximum volume flow
Hysteresis preset value exceedence ∆t-contr.-min.
Hysteresis preset value underrun
Week timer
Factory setting
Typen:
Parameter
P
Balance values
B
Meas. values
M
Status value
S
Constants
K
4.

Functions and Options

4.1
Circulation (demand version)
Options/Circulat.
Adjustment range No, demand, therm
Factory setting No
Settings/circ.run
Adjustment range 1 - 10 min
Factory setting 2 min
Settings/circ.wait
Adjustment range 00:00 - 00:20 min
Factory setting 00:10 min
4.2
Circulation (thermal version)
Options/circulat.
Adjustment range No, demand, therm.
Factory setting No
Settings/week timer circ.
(only visible when thermal circulation is activated )
Adjustment range t1 - t21 on / off
Menu code
Type
P
Hot water
P
bp on
P
bp off
P
bp wait
S
-block. protect.
P
bp time
P
Rot. min.
P
Start imp..
P
Tap min.
P
mx. flow
P
P
∆t-contr.-on
P
Time
P
Factory setting
A short impulse starts the circulation pump.
The pump is started up for an adjusted time span (circulation
run time). When the run time is over, the restart demand
for the circulation will be blocked for a set time span
(circulation holding time).The active function is displayed.
The temperature of the hot water line will be checked
within a specified time frame (week timer (WT)) and with
the help of sensor T-C. If the pre-adjusted minimum tem-
perature is underrun (Circ.min), the circulation pump will
be started up. It will be shut off again after the hot water
line has been heated up by the adjusted heat hysteresis.The
sensorT-C can either be connected to sensor S5, S6 or S7
(T-CW) (factory setting S7).
The minimum circulation temperature (Circ.min) is linked
to the hot water temperature and the circulation hysterisis
and will be automatically adjusted.
The active function is displayed.
Range
45 ... 65 °C
00:00-23:59
00:00-23:59
30 min ... 6 h
1 s ... 10 s
12 % ...100 %
1 s ... 5 s
30 l/h .. 300 l/h
0 l/h ... 9999 l/h
0 K ... 10 K
0 K ... 25 K
Mo. 00:00 ... Su. 23:59
Yes ... No
Factory Setting
55 °C
06:00
20:00
4 h
4 s
12 %
1 s
90 l/h
1550 l/h
5 K
-5 K
Su 12:00
No
23
|
Tabla de contenido
loading

Tabla de contenido