Pressure adjustment at the burner
Since this unit has flame modulation, there are two fixed pressure settings: minimum and
maximum, which must be those given in the technical data table according to the type of
gas.
Connect a suitable pressure gauge to the pressure point "B" downstream of the
gas valve.
Activate the TEST mode (see cap. 4.1).
Press the Eco/Comfort button for 2 seconds to access the gas valve Calibration
mode.
The card goes to the setting "q02"; displaying the actually saved value, by pressing
the DHW buttons .
If the pressure gauge reading is different from the nominal maximum pressure, pro-
ceed by increases/decreases of 1 or 2 units of parameter "q02" by pressing the
DHW buttons : the value is stored after each modification; wait 10 seconds for the
pressure to stabilise.
Press the heating button "-" (ref. 3 - fig. 1).
The card goes to the setting "q01"; displaying the actually saved value, by pressing
the DHW buttons .
If the pressure gauge reading is different from the nominal minimum pressure, pro-
ceed by increases/decreases of 1 or 2 units of parameter "q01" by pressing the
DHW buttons : the value is stored after each modification; wait 10 seconds for the
pressure to stabilise.
Recheck both adjustments by pressing the heating buttons and adjust them if nec-
essary by repeating the above procedure.
Press the Eco/Comfort button for 2 seconds to return to the TEST mode.
Deactivate the TEST mode (see cap. 4.1).
Disconnect the pressure gauge.
A - Upstream pressure point
B - Downstream pressure point
R
I - Gas valve electrical connection
R - Gas outlet
S - Gas inlet
B
I
TYPE SGV100
A
Pi max 65 mbar
24 Vdc - class B+A
S
fig. 18 - Gas valve
Heating power adjustment
To adjust the heating power, switch the boiler to TEST mode (see sec. 4.1). Press the
heating buttons detail 3 - fig. 1 to increase or decrease the power (min. = 00 - max. =
100). Press the reset button within 5 seconds and the max. power will remain that just
set. Exit TEST mode (see sec. 4.1).
6
EN
1 2 3 4
~ 24W
fig. 19 - Gas valve connection
cod. 3541F121 - Rev. 01 - 03/2018

Configuration Menu

Press the DHW buttons together for 10 seconds to access the configuration Menu. 8 pa-
rameters are available, indicated by the letter "b", which are not modifiable from Remote
Timer Control.
Press the Heating buttons to scroll the list of parameters in increasing or decreasing or-
der. Press the DHW buttons to view or modify the value of a parameter: the modification
will be automatically saved.
Contents
Description
b01
Gas type selection
b02
Boiler type selection
Combustion chamber
b03
type selection
~ 65W
Primary Exchanger
type selection
(b03=0)
No effect on adjust-
ment (b03=1)
No effect on adjust-
ment (b03=2)
b04
Primary Exchanger
type selection
(b03=3)
No effect on adjust-
ment (b03=4)
No effect on adjust-
ment (b03=5)
Auxiliary relay card
(b02=1)
operation selection
(b02=1)
No effect on adjust-
b05
ment (b02=2)
No effect on adjust-
ment (b02=3)
No effect on adjust-
ment (b02=4)
Mains Voltage Fre-
b06
quency
Comfort burner on
time
(b02=1)
No effect on adjust-
b07
ment (b02=2)
No effect on adjust-
ment (b02=3)
No effect on adjust-
ment (b02=4)
b08
Driver Gas valve
Notes:
1.
Parameters with more than one description vary their function and/or range in rela-
tion to the setting of the parameter given in brackets.
2.
Parameters with more than one description are reset to the default value if the pa-
rameter given in brackets is modified.
To exit the configuration Menu press the DHW buttons together for 10 seconds, or exiting
occurs automatically after 2 minutes.
FL 24 MCS
Range
Default
0=Natural Gas
0=Natural Gas
0=Natural Gas
1=LPG
1=Bithermal instanta-
neous
2=Monothermal
instantaneous
1=Bithermal instanta-
2=Monothermal
neous
instantaneous
3=Heating only (3-way
valve)
4=Heating only (circu-
lating pump)
0=Sealed Chamber
combustion control
(without fume pres-
sure switch)
1=Open Chamber
(with fume thermostat)
2=Sealed Chamber
(with fume pressure
switch)
0=Sealed Chamber
0=Sealed Chamber
with
3=Sealed Chamber
with
combustion control
combustion control
combustion control
(without fume pres-
(with fume thermostat
sure switch)
on recuperator)
4=LOW NOx Sealed
Chamber Combustion
control
(without fume pres-
sure switch)
5=LOW NOx Open
Chamber
(with fume thermostat)
0=Flat
1=Omega
0=Flat
0=Flat
2=--
--
0
--
0
0=Flat
1=Omega
0=Flat
2=--
--
0
--
0
0=External gas valve
1=System filling sole-
0=External gas valve 0=External gas valve
noid valve
2=Solar 3-way valve
--
0
--
0
--
0
0=50Hz
0=50Hz
0=50Hz
1=60Hz
0-20 seconds
5 seconds
5 seconds
--
5
--
5
--
5
0 = Standard, 1
0=Standard
0=Standard
FL 24 MCS