Wiring Heat Pump Systems - Honeywell T6 Pro Manual De Instrucciones

Ocultar thumbs Ver también para T6 Pro:
Tabla de contenido
Idiomas disponibles

Idiomas disponibles

Wiring heat pump systems

Shaded areas below apply only to TH6320U/TH6220U or as otherwise noted.
1H/1C Heat Pump System
R
Power [1]
Rc
[R+Rc joined by Slider Tab] [2]
Y
Compressor contactor
C
24VAC common [3]
O/B Changeover valve [7]
G
Fan relay
2H/1C Heat Pump System [8]
R
Power [1]
Rc
[R+Rc joined by Slider Tab] [2]
Y
Compressor contactor
C
24VAC common [3]
O/B Changeover valve [7]
G
Fan relay
Aux Auxiliary heat
E
Emergency heat relay
L
Heat pump fault input
2H/2C Heat Pump System
(TH6320U only) [9]
R
Power [1]
Rc
[R+Rc joined by Slider Tab] [2]
Y
Compressor contactor (stage 1)
C
24VAC common [3]
O/B Changeover valve [7]
G
Fan relay
Y2
Compressor contactor (stage 2)
L
Heat pump fault input
NOTE: Do NOT use W for heat pump applications. Auxiliary heat must wire to AUX or E.
NOTES
Wire specifications: Use 18- to 22-gauge thermostat wire. Shielded cable is not required.
[1] Power supply. Provide disconnect means and
overload protection as required.
[2] Move R-Slider Tab on UWP to the R setting.
For more information, see "Setting Slider Tabs"
on page 3
[3] Optional 24VAC common connection.
[6] In Installer Setup, set system type to
2Heat/2Cool Conventional.
[7] In Installer Setup, set changeover valve to O
(for cool changeover) or B (for heat change-
over).
3H/2C Heat Pump System
(TH6320U only) [10]
R
Power [1]
Rc
[R+Rc joined by Slider Tab] [2]
Y
Compressor contactor (stage 1)
C
24VAC common [3]
O/B Changeover valve [7]
G
Fan relay
Aux Auxiliary heat
E
Emergency heat relay
Y2
Compressor contactor (stage 2)
L
Heat pump fault input
Dual Fuel System (TH6320U / TH6220U only)
R
Power [1]
Rc
[R+Rc joined by Slider Tab] [2]
Y
Compressor contactor (stage 1)
C
24VAC common [3]
O/B Changeover valve [7]
G
Fan relay
Aux Auxiliary heat
E
Emergency heat relay
Y2
Compressor contactor (stage 2 - if
needed) [11]
L
Heat pump fault input
S
Outdoor sensor
S
Outdoor sensor
[8] In ISU set Heat system type to Heat pump. 1
compressor and 1 stage of backup heat.
[9] In ISU set Heat system type to Heat pump. 2
compressors and 0 stage of backup heat.
[10]In ISU set Heat system type to Heat pump. 2
compressors and 1 stage of backup heat.
[11] Dual fuel with Y2 only for TH6320U.