Bosch FCS‑320‑TP Serie Guía De Instalación Rápida página 17

Tabla de contenido
Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 22
Conventional aspiration smoke detector
5.
6.
3
Connection
For motherboard with terminal blocks X6 and X7, refer to graphic 03, page 4 .
Terminal Terminal block X6 Function
1
2
3
4
5
6
7
8
9
Terminal Terminal block X7
1
2
3
4
5
6
7
8
9
Notice!
On Bosch fire panels, use R
resistor.
Parameter settings using the DIP switch
The aspirating smoke detector parameters are set using the DIP switch on the detector
modules. The default settings are marked in bold in each case. Select all other parameters
(see tables).
Sensitivity
DM-TP-01(05)
DM-TT-01(05)
0.12%/m
Bosch Sicherheitssysteme GmbH
Route the connection cable(s) (max. 2.5 mm2) through the prepared M20 or M25
connections and into the unit. Now cut these to the required length inside the unit.
Wire the unit according to the connection information described below.
Al 1
+ Ext. Displ.1
- Ext. Displ.1
+ Reset
- Reset
+ 24 V
- 24 V
Fault 2
Al 2
+ Ext. Displ.2
- Ext. Displ.2
Fault 1
A
DM-TP10(25)
DM-TT-10(25)
0.8%/m
Quick installation guide
NO contact for 1st alarm relay
C contact for 1st alarm relay
NC contact for 1st alarm relay
Remote indicator for 1st detector module
+24 V reset input
0 V reset input
+24 V power supply
0 V power supply
Fault contact for 2nd detector module
NO contact for 2nd alarm relay
C contact for 2nd alarm relay
NC contact for 2nd alarm relay
Remote indicator for 2nd detector module
Fault contact for 1st detector module
820 Ohm for the alarm resistor and RE 2k2 (3k9) for the terminal
DM-TP50(80)
DM-TT-50(80)
-
Connection | en
DIP settings
Switch 1
Switch 2
on
on
2020.04 | 3 | F.01U.130.927
17
Tabla de contenido
loading

Este manual también es adecuado para:

Fcs-320-tp1Fcs-320-tp2

Tabla de contenido