single structure installations
A
Exhaust
Direction
B
5 ft (1.5 m)
two structure installations
Structure
18 in (45.7 cm) min
5 ft (1.5 m) min
Standby
Exhaust
Direction
A
A
Structure
5 ft (1.5 m) min
Standby
Shrubs, Tree or
Vegitation
A
5 ft
(1.5 m)
B
18 in (45.7 cm) min
Standby
B
Exhaust
Direction
Structure
18 in (45.7 cm) min
Standby
Exhaust
Direction
5 ft (1.5 m)
A
Legend for Generator Locations to reduce the risk of fire.
Standby weatherproof enclosure must be at least 5 ft
A
(1.5 m) from windows, doors, any wall opening, shrubs
or vegetation over 12 inches (30.5 cm) in height.
Exhaust outlet side of weatherproof enclosure must
B
have at least 5 ft (1.5 m) minimum clearance from any
structure, shrubs, trees or any kind of vegetation.
Standby weatherproof enclosure must have a
C
minimum of 4 feet (1.2 m) overhead clearance from
any structure, overhang or trees.
NOTICE DO NOT place weatherproof enclosure under a deck
or other type of covered structure that may confine airflow.
A
Structure
5 ft (1.5 m) min
5 ft (1.5 m)
A
5 ft (1.5 m) min
B
13