Safety Notes
NOTICE!
Installation must only be performed by authorized and specialized personnel.
CAUTION!
Electrostatic discharge (ESD)! Electronic components could become damaged.
Ground yourself using a wrist strap or take other suitable actions.
Functional description
FLM-420-I2 input interface modules provide three monitoring functions:
-
Monitoring a line with EOL resistor for standby or triggering (interruption/short circuit)
-
Monitoring a potential free contact for "open" and "closed" states
-
Voltage monitoring between 0 and 30 V DC.
The FLM-420-I2-D is installed on a DIN rail in accordance with EN 500022 with enclosed adapter (see Figure 1,
Page 4, Removal: Figure 2, Page 5).
Address Setting
Fit the rotary switches in the required position using a pan head slotted screwdriver
(see Figure 3, Page 6).
Address (A)
Operating mode
0 0 0
Loop/stub in LSN improved version mode with automatic addressing
0 0 1 - 2 5 4
Loop/stub/T-taps in LSN improved version mode with manual addressing
CL 0 0
Loop/stub in LSN classic mode (address range 127 max.)
2 5 5 - 2 9 9
Invalid address range (error message on fire panel)
Connection
See Figure 4, Page 6.
Description
LSN: b1+ | a- | b2+
IN: IN1+ | IN1- | IN2+ | IN2-

Technical specifications

Inputs
LSN input voltage
Max. current consumption from LSN
Contact monitoring:
-
EOL resistor
-
Max. current strength (current pulse)
-
Total resistance of the line
Voltage monitoring:
-
Voltage range
-
Input resistance
-
Number of selectable threshold values
Permissible wire diameter
Cable length per input
Permissible operating temperature / storage temperature
Permissible rel. humidity
Protection class as per IEC 60529
Classes of equipment as per IEC 60950
Housing material and color
Dimensions (with adapter, W x H x D)
Bosch Sicherheitssysteme GmbH
Function
LSN b incoming / LSN a / LSN b outgoing
Input 1 | Input 2
2, independent
15 to 33 V DC
10.4 mA
Nominal, 3.9 kΩ
8 mA
-
-
-
0 to 30 V DC
> 50 kΩ
4 (see programming software)
0.6 to 3.3 mm
Max. 3 m
-20 °C to +65 °C / -25 °C to +80 °C
<96 %, non-condensing
IP 30
III
PPO (Noryl), gray white (similar to RAL 9002)
Approx. 110 mm x 110 mm x 48 mm
In standby: 1500 Ω to 6000 Ω
Short-circuit: < 800 Ω
Interruption: > 12000 Ω
2
en
11
F.01U.012.988 | 5.0 | 2011.10