Installation manual
1
About this manual
Manual code: DCMIIN1PPFMEXT
Version: 1.30
2
General Description
The IFMEXT and FPMEXT are fire-extinguishant system control modules and must be combined.
The internal IFMEXT module allows management of a gas extinguishant channel. Complies with EN12094-1
and provides the inputs, outputs and control logic required by fire-extinguishant systems.
The indications provided by the IFMEXT module, as well as being visualized on the FPMCPU module display,
can also be seen on the LEDs on the front-plate FPMEXT module. This module has 40 tricolour LEDs which
replicate the signals of up to 5 IFMEXT.extinguishant modules on the control panel front plate.
FPMEXT comes with:
• CAN BUS cable
• 6 screws with washers for securing the module
• 1 ferrite
• Instructions manual
Figure 1 - FPMEXT, page 1
[A]
Visual signalling of IFMEXT modules
[B]
Mounting screw locations
Connector for the CAN drive bar or
[C]
other front-plate module
[D]
Connector for front-plate module
[E]
Mini USB port
[F]
Module firmware version label
About this manual
FPMEXT module - technical specifications
Power supply voltage
Operating temperature
stand-by
Consumption @
27.6V
maximum
19-30 V
supplied by IFM24160 module
from -5°C to +40°C
12mA
45mA
5