6. Technical data
Reliable isolation
• I/O (Analog), I/O (Relay)
Test voltage:
• I/O (Analog), I/O (Relay), I/O (Transistor), I/S
• O (Analog)/O (Relay), O (Relay)/O (Transistor)
• O(Analog)/O(Transistor), O (Analog)/S
Surge voltage category
Contamination class
Ambient temperature range
Module warm-up time
Function standby signal
Protection type
Installation position/mounting
Dimensions (W / H / D) in mm
Conductor cross section
Type of housing
1)
If the maximum values indicated are exceeded, the gold layer is destroyed! The following max.
switching voltages and currents are then valid for further operation: 250 V AC/DC; 2A.
=
=
2)
I
Input / O
Output / S
3)
Suitable for measuring in 400 V AC three-phase system.
Conformity / approvals
Conformance
Conformance
Immunity to interference
Noise emission
UL approval
2)
,I/O (Transistor), I/S
operation
=
Supply
with low voltage directive 2006/95/EC
with EMC directive 2004/108/EC
according to EN 61000-6-2
according to EN 61000-6-4
U
PROCESS CONTROL EQUIPMENT
FOR HAZARDOUS LOCATIONS
LISTED
31ZN
Cl. I, Zn. 2, AEx nC IIC T6 / Ex nC IIC T6
Cl. I Div. 2, Groups A, B, C and D or Non-Hazardous Locations Only
A) This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or
non-hazardous locations only.
B) Warning - explosion hazard - substitution of components may impair suitability
for Class 1, Division 2,/Zone 2.
C) Warning - explosion hazard - do not disconnect equipment unless power has
been switched off or the area is known to be non-hazardous.
acc. to EN 50178, EN 61010:
300 V AC to earth
4 kV, 50 Hz, 1 min.
4 kV, 50 Hz, 1 min.
500 V, 50 Hz, 1 min.
III
2
-20 °C to +60 °C
storage
-40 °C to +85 °C
> 2 min.
green LED
IP 20
any
22.5 x 99 x 114.5
0.2 – 2.5 mm
polyamide PA non-reinforced
c
3)
2
(AWG 24-14)
27